BS – Cable Size Under Short Circuit Calculation
- Last UpdatedJul 14, 2025
- 5 minute read
This section describes the fault current calculation that needs to be performed after the cable has been sized.
The adiabatic method shown below calculates maximum short circuit current. The larger the cable, the larger the current the cable can withstand without damage.
Step – I Calculate Source Short Circuit Current
ISC = (Er * 1000) * (100)
V * (Imp %)
Where:
V = Phase voltage (Vph * Ö3/2) for 1 phase, Line voltage Vl for 2 phase or Line voltage (Vl * Ö3) for 3 phase
Er = Equipment rating with units in kVA
Imp % = Equipment Impedance expressed as a percentage
Step – II Calculate Source Impedance
Zsc = V/Isc
Where:
Zsc = source impedance in ohms
Isc = phase current in amps
V = voltage in volts

Step – III Calculate Cable Impedance 1 (When cable catalogue has valid values)
If the cable catalogue data includes the resistive and reactive value then use the following equation:
Zc1 = (L/1000) * Ö[(Rc)2 + (Xc)2]
Where:
L = length in meters
Rc = resistance of active conductor (Ohms/km)
Xc = reactance of active conductor (Ohms/km)
Zc1 = cable impedance in Ohms
Step – IV Calculate Cable Impedance 1 (If No cable catalogue values)
If conductor resistive and reactive values are not available in the cable catalogue, then impedance values are taken from BS standard impedance tables.
Zc1 = ([(R * L * cosø) / A] + [X * L * sinø])
Where:
R = Resistivity of conductors in normal service, taken equal to the Resistivity at the temperature in normal service, i.e. 1.25 times the Resistivity at 20°C, or 0.0225Wmm2/m for copper and 0.036Wmm2/m for aluminium
L = route length of circuit, in metres
A = cross-sectional area of conductors, in mm2
cosø = power factor; in the absence of precise details, the power factor is taken as 0.8 (sin ø = 0.6)
X = reactance per unit length of conductors, which is taken to be 0.00008W/m in the absence of other details
Zc1 is in Ohms

If cables are in parallel (see the screen shot above) the ‘No. of Cables:’ value will be 2 or more (in future).
The equation to find the total impedance is:
1/ZTOTALc1 = 1/Zc1A + 1/Zc1B + 1/Zc1C …….+ 1/Zc1n
Where:
ZTOTALc1 = total impedance for cable in ohms
1/Zc1A = impedance for cable if ‘No. of Cables:’ value = 1, in ohms
1/Zc1B = impedance for cable if ‘No. of Cables:’ value = 2, in ohms
1/Zc1C = impedance for cable if ‘No. of Cables:’ value = 3, in ohms
1/Zc1n = impedance for cable if ‘No. of Cables:’ value = n, in ohms
Since system only allows 2 cables to be in parallel the equation can be simplified to:
ZTOTALc1 = Zc1/N
Where:
Zc1 is in Ohms
N = number of cables in parallel, N = 1 when no cable in parallel
Step - V Calculate Cable Impedance 2 (If No cable catalogue values)
In this example there is a cable between switchboard busbar SWB-2 and incomer MCC-1.
Before performing the calculation the system needs to check if it is a power cable.
Then if there is an impedance value for the cable.
Then if it is in parallel.
The calculation is exactly the same as the Cable Impedance 1 calculation.

Step – VI Calculate Total Impedance
Z = Zsc + ZTOTALc1N + ZTOTALc2 + ……. + ZTOTALcn
Where:
Z is total impedance for Isc in ohms
Zsc = source impedance in ohms
ZTOTALc1 = total impedance for cable in ohms
ZTOTALc2 = total impedance for cable in ohms
ZTOTALcn = total impedance for cable in ohms
Step – VII Calculate Short Circuit Current for Sized Cable
Isc = V/Z
Where:
Isc is short circuit current in amps
V is voltage in volts
Z is total impedance for Isc in ohms

Step - VIII Calculate Korg Factor
-
Find the Initial Temperature
Initial Temperature = Conductor Temp (from the Lookup Current Rating Table)
-
Find the Final Temperature (default values are shown in the table below)
Limit
Insulation Type
Cond. Temp
Core Size
Final Temperature
160
Thermoplastic
70
<= 300 mm2
140
Thermoplastic
70
> 300 mm2
250
Thermosetting
90
160
Mineral
70
250
Mineral
105
-
Find the Material K Factor (from Lookup table - see below)
b is the reciprocal of temperature coefficient of resistance of the current carrying component at 0°C
This K factor is based on BS 7454:1991+A1:2008.
Material
Material Factor
(b)
K Factor Lookup
Cu
226
234.5
Al
148
228
Refer to also the Beta value against materials
-
Find the Korg Factor using this formula:
Korg = Ö[(Material Factor)2 * Log [(Final Temperature + b) / (Initial Temperature + b)]]

A = Ö((Isc/P)2 * t)/Korg
Step – IX Calculate Core Size based on Short Circuit Current
A = Ö((Isc/P)2 * t)/Korg
Where:
A is the cross-sectional area of the current-carrying component, in square millimetres.
Isc is the short-circuit current
t is the duration of short circuit
Korg is constant
P is the number of conductors in parallel
The results of this calculation are displayed in the Sizing Result tab as shown below: