Nameplate Connected Power

  • Last UpdatedNov 21, 2023
  • 2 minute read

Nameplate Connected Power

  • Nameplate Connected Power has a unit value of kW.

  • Nameplate Connected Power is the total active power for all fed equipment tags.

  • Nameplate Connected Power is derived from Nameplate Power.

The equation for Nameplate Connected Power is:

Nameplate Connected Power Power = å Nameplate Power

Nameplate Connected Reactive Power

Nameplate Connected Reactive Power is the reactive power passing through a tag (Supply Tag).

  • Nameplate Connected Reactive Power has a unit value of kVAr.

  • Nameplate Connected Reactive Power can have a positive or negative value. If positive, the associated power factor unit = LAG and if negative, the associated power factor unit = LEAD.

  • Nameplate Connected Power is the total reactive power for all fed equipment tags.

The equation for Nameplate Connected Reactive Power attributes is:

Nameplate Connected Reactive Power = å Nameplate Reactive Power

Nameplate Connected Apparent Power

Nameplate Connected Apparent Power is calculated using Nameplate Connected Active Power and Nameplate Connected Reactive Power.

Nameplate Connected Power has a unit value of kVA.

The equations for Nameplate Connected Power is:

Nameplate Connected Apparent Power = √ (Nameplate Connected Power2 + Nameplate Connected Reactive Power2)

Nameplate Connected Power Factor

Nameplate Connected Power Factor is calculated using Nameplate Connected Active Power and Nameplate Connected Apparent Power

Nameplate Connected Power Factor has a unit value of ratio. The equation for Nameplate Connected Power Factor is:

Nameplate Connected Power Factor = Nameplate Connected Power / Nameplate Connected Apparent Power

Equations for Nameplate Connected Power Factor Unit attributes are:

If Nameplate Connected Reactive Power value is positive then Nameplate Connected Power Factor Unit = LAG

If Nameplate Connected Reactive Power value is negative then Nameplate Connected Power Factor Unit = LEAD

If Nameplate Connected Reactive Power value = 0 then Nameplate Connected Power Factor Unit = null

Nameplate Connected Current

Nameplate Connected Current is calculated using Connection Voltage data (Voltage Type, Project Voltage) and Nameplate Connected Apparent Power.

Nameplate Connected Current has a unit value of Amp.

Equations for Nameplate Connected Current attributes are:

If Voltage Type = S then
Nameplate Connected Current = (Nameplate Connected Apparent Power * 1000) / Project Voltage

If Voltage Type = L then
Nameplate Connected Current = (Nameplate Connected Apparent Power * 1000) / Project Voltage

If Voltage Type = T, TN then
Nameplate Connected Current = (Nameplate Connected Apparent Power * 1000) / (Project Voltage * 3)

If Voltage Type = DC then
Nameplate Connected Current = (Nameplate Connected Power * 1000) / Project Voltage

Note:
In this case Nameplate Connected Apparent Power = Nameplate Connected Power.

Nameplate Connected Full Load Current per Phase

Nameplate Connected Full Load Current per Phase is calculated using Connection Voltage data (Project Voltage) and Nameplate Connected Apparent Power per Phase.

Nameplate Connected Full Load Current per Phase has a unit value of Amp.

Equation for Nameplate Connected Full Load Current per Phase is:

Nameplate Connected Full Load Current per Phase = (Nameplate Connected Apparent Power per Phase * 1000) / Phase Voltage

Note:
Line Voltage = Phase Voltage * √3