Process description for the U5 example simulation
- Last UpdatedSep 20, 2024
- 1 minute read
The fire water supply temperature is 25.5°C (78°F) and pressure is 2170 kPa (300 psig).
In the revamped network, all fire water delivery points will have a minimum flow requirement of 0.0158 m3/s (250 gpm) and a minimum pressure requirement of 1032 kPa (135 psig).
Details of the fire water delivery points are as follows:
|
Existing Delivery Points |
SNK1, SNK2, SNK3, SNK4, SNK7, SNK8, SNK9, SNK10 |
|
New Expansion Delivery Points |
SNK5, SNK6 |
The fire water pumping station will take care of additional fire water flow requirements.
Details of existing pipe network are as follows:
|
Pipe |
Size NPS (in.) |
Schedule |
L (m) |
DE (m) |
|---|---|---|---|---|
|
PIPE1 |
6 |
40 |
30 |
0 |
|
PIPE2 |
6 |
40 |
30 |
0 |
|
PIPE3 |
6 |
40 |
91 |
0 |
|
PIPE4 |
6 |
40 |
305 |
0 |
|
PIPE5 |
4 |
40 |
152 |
0 |
|
PIPE9 |
4 |
40 |
152 |
0 |
|
PIPE10 |
6 |
40 |
305 |
0 |
|
PIPE11 |
4 |
40 |
152 |
0 |
|
PIPE12 |
6 |
40 |
914 |
0 |
|
PIPE13 |
3 |
40 |
91 |
0 |
|
PIPE14 |
3 |
40 |
91 |
0 |
|
PIPE15 |
3 |
40 |
91 |
0 |
|
PIPE16 |
3 |
40 |
91 |
0 |
|
PIPE19 |
3 |
40 |
91 |
0 |
|
PIPE20 |
3 |
40 |
91 |
0 |
|
PIPE21 |
3 |
40 |
91 |
0 |
|
PIPE22 |
3 |
40 |
91 |
0 |