Fluid Flow mode results for the F1 example simulation

Fluid Flow mode results for the F1 example simulation

  • Last UpdatedOct 04, 2024
  • 1 minute read

The following table shows the relief valve back pressures for the case in which total power failure occurs (FF2) at the required flow conditions.

Variable

Name

UOM

RV1

RV2

RV3

RV4

Mass flow

W

kg/h

10000

0

30000

40000

Set pressure

SP

kPa

1726.07

1271.52

816.98

362.43

Area

A

mm2

1840

4116

10322

20644

Capacity

Capacity

%

62

0

63

80

Inlet pressure

P1

kPa

2000

1400

1000

500

Back pressure

Pb

kPa

685

178

204.5

188

Back pressure fraction

BPf

%

33.8

6.2

12.6

23.85

Relief valve RV1 has a high back pressure. We analyze the inlet and tail pipes at RV1 and find that tail pipe PT1 is undersized. The following table shows the tail pipe sizing in which relief valve RV1 is at rated flow conditions. Values in the Original column represent the current simulation data which do not meet design criteria. Values in the Recommended column represent enlarged inlet and tail pipes to satisfy the 3% rule and 10% superimposed backpressure.

Variable

Name

UOM

Original

Recommended

Mass flow

W

kg/h

16224

16224

Diameter

D

NPS

4 in

8 in

Length

L

m

20

20

Outlet velocity

Vel2

m/s

508

203

Outlet Mach

Ma2

1.0

0.40

Pressure drop

DP

kPa

406

22.5

Back pressure fraction

BPf

%

33.8

15.7