AVEVA™ Process Simulation

Dynamics mode results for the U2 example simulation

Dynamics mode results for the U2 example simulation

  • Last UpdatedOct 04, 2024
  • 1 minute read

Changing the setpoint pressure (PC1.SP) from 4500 kPa to 4750 kPa and running dynamics demonstrates the dynamic response of the turbine. Different PID controller tuning parameters can improve the response. The following figure trends the header pressure change due to a change in set point with the controller (PC1) tuning parameters from the following table.

Description

Var/Par

Value

Units

Control range high valve

PVHi

5000

kPa

Control range low valve

PVLo

1000

kPa

Proportional Gain

Kp

10

Integral time

Ti

20

s

Derivative time

Td

0

s

Embedded Image (65% Scaling) (LIVE)