Wonderware Galaxy Integration Attributes - General tab
- Last UpdatedFeb 21, 2025
- 2 minute read
-
Title: This required field, limited to 255 characters, aids in the identification of this Integration.
-
Tag Name: Enter the ArchestrA Tag Name appropriate for this instance of the ArchestrA Integration, or click the ellipsis (
) button to display the Galaxy Browser to assist in Tag selection.
Note: Tag browsing is only supported if the ArchestrA IDE and Bootstrap are installed on the computer running this instance of the AVEVA Mobile Operator Client.
-
Integration Type: Select "Server" to enable transfer to ArchestrA upon synchronization, or "Mobile" to enable instant transfer in the field using a wireless connection. The instant transfer uses the local time of Mobile Operator ArchestrA Update Service.
Important:
- When using the "Mobile" Integration Type, be sure to check "Server" as well. This will ensure that the data is delivered upon synchronization in case the Mobile delivery fails. Otherwise, data transfer will not be attempted again.
- When using the “Mobile” Integration Type, ensure the Mobile Operator Archestra Update Service and the Mobile Operator app are on the Mobile Operator 2020 R2SP1 version and above.
The following points allow modification of the time-stamping options used for this instance of the integration. Select the option appropriate for your needs from the following.
-
Timestamp of Task: Uses the time at which input was last provided to the Task.
-
Fixed Timestamp: Uses a user-configured, fixed timestamp:

Note: "Fixed Timestamp" uses the time at which input was last provided to the Task to determine the "current" date.
Enter the desired time in the provided text field, and optionally a number of days to offset the timestamp into the past (where 0 is the current day, 1 is one day before the current day, et cetera).
-
Timestamp of Procedure Node: If applicable, the time input was last provided to the Task Group’s status question or Task’s question, or the last calculation evaluation of a Decision. Otherwise, the timestamp of the last time this Task Group was navigated away from.
-
Value of Selected Task: Uses the value of this task as the timestamp. This is only intended for Tasks that use an input type of "Datetime."
Note: AVEVA Application Server receives all timestamps in UTC (Universal Coordinated Time) format. For example, German time zone is 2 hours ahead of UTC. When answering a task at 1 PM in the German time zone, the Object Browser application in System Platform displays the timestamp as 11 AM (as per UTC).