Configure the Downtime Event Table
- Last UpdatedFeb 25, 2025
- 4 minute read
There are several steps to complete in the configuration of the Event Table matrix. This is an advanced procedure to perform.
-
Configure SCADA
-
Configure the connection
-
Set Event Table properties
-
Populate the Event Table fields
-
Define Event Masks
-
Turn on EnableEventTableLookup property
-
Define Event Areas
-
Configure Effect Mappings
1. Configure SCADA
These screens show examples only of SCADA configuration. They are provided for illustrative purposes only and occur outside of AVEVA™ Production Management. There are many ways to configure SCADA or your external source database and an experienced engineer configures this part of the procedure.
Example:
-
Configure SCADA to log alarms to an SQL Table named EventTable.

-
Configure a SCADA Alarm Category. Be certain that you set the Log Device to the device you created in step 1.

2. Configure the connection
In Studio, configure the database connection details for the OLE-DB connection item.
For more information on the database connection properties, see Downtime database connection properties.
3. Set Event Table properties
In Studio, configure the connection details for the EventTable item.

For more information on the database connection properties, see Downtime Event Table properties.
4. Populate the Event Table fields
-
Navigate to System Configuration > Downtime > Events > Event Table, right-click the Fields folder, and select Populate Fields.

-
For each populated field, configure the Field Type and Field ID Type properties.


Set the FieldIDType for these fields as specified in this table.
|
Field |
FieldIDType |
|
|
Tag |
EventName |
|
|
Area |
EventArea |
|
|
OnDateTime |
EventTime |
5. Define Event Masks
-
Specify the EventMask properties for Applications folders on the plant hierarchy.

The EventMask property is a regular expression used to determine the cause location from the list of possible events. This property supports a regular expression.
Example
For example, an EventMask of 2020CV.+ matches any EventName that contains 2020CV followed by at least one other character, such as ABC2020CV1, 2020CVTOL.
From the filtered list of events captured in the time window, the regular expressions are used to match an event mask with an event. A match occurs when the EventName field matches the EventMask regular expression on a folder in the plant hierarchy. The match process starts from the top of the hierarchy and works down. When a match is established, the cause location is identified.
It is important to be certain that only a single cause location results from the matching process.
6. Turn on EnableEventTableLookup property
-
Set the value on the EnableEventTableLookup property of the relevant Downtime reporting point to True.

7. Define Event Areas
If the plant contains parallel processes, it may be helpful to limit possible events/alarms to the areas in which you are interested.
Example
StationA and StationB. The stations are two separate processes and an alarm in StationA is not relevent to Downtimes in StationB. To restrict the list of possible Downtime-causing alarms, each Downtime Reporting Point has an EventsAreas property.
-
Specify the EventAreas properties for Downtime reporting points on the plant hierarchy.

The values entered into the EventAreas property should align with the area values associated with the alarms from the SCADA system.
8. Configure Effect Mappings
Add effect mapping items to the effect mapping parent and configure each item.

A matching process, like determining the cause location, also takes place to determine the effect.
This time, the EventName is matched against the regular expressions configured for each of the Effect items. When a match is established, the string value of the Effect property is selected for inclusion into the Downtime record.
After a match is established the Downtime record is populated with the event, effect, and cause location as defined by the CaptureDataWhen property for the field; for example, DowntimeStateOff.
Example
An event mask of .+TOL$ matches any event name that contains at least one other character and ends with TOL.
Example of returned results:
2020CVTOL - AVEVA™ Production Management chooses the event ending in TOL.
2020CVBLK