Max Demand Connected Power

  • Last UpdatedApr 08, 2024
  • 2 minute read

This is the combination of Continuous and Intermittent absorbed power.

Max Demand Conn Power

  • Max Demand Conn Power has a unit value of kW.

  • Fed tag Diversity has a unit of ratio.

  • Max Demand Conn Power is the summation of the following Utilizations for each fed tag. The utilization values are:

    • Continuous

    • Intermittent

The equation for Max Demand Conn Power is:

Max Demand Conn Power = (Σ Continuous Power + Σ Intermittent Power)

Max Demand Conn Reactive Power

  • Max Demand Conn Reactive Power has a unit value of kVAr.

  • Max Demand Conn Reactive Power can have a positive or negative value. If positive, the associated power factor unit = LAG and if negative, the associated power factor unit = LEAD.

  • Fed tag Diversity has a unit of ratio.

The equation for Max Demand Conn Reactive Power is:

Max Demand Conn Reactive Power = (Σ Continuous Reactive Power + Σ Intermittent Reactive Power)

Max Demand Conn Apparent Power

Max Demand Conn Apparent Power is calculated using Max Demand Conn Power and Max Demand Conn Reactive Power.

Max Demand Conn Apparent Power has a unit value of kVA.

The equation for Max Demand Conn Apparent Power is:

Max Demand Conn Apparent Power = √ (Max Demand Conn Power2 + Max Demand Conn Reactive Power2)

Max Demand Conn Power Factor

Max Demand Conn Power Factor is calculated using Max Demand Conn Power and Max Demand Conn Power Apparent Power

Max Demand Conn Power Factor has a unit value between 0 and 1.

The equation for Max Demand Conn Power Factor is:

Max Demand Conn Power Factor = Max Demand Conn Power / Max Demand Conn Apparent Power

Equations for Max Demand Conn Power Factor Unit attributes are:

If Max Demand Conn Reactive Power value is positive then Max Demand Conn Power Factor Unit = LAG

If Max Demand Conn Reactive Power value is negative then Max Demand Conn Power Factor Unit = LEAD

If Max Demand Conn Reactive Power value = 0 then Max Demand Conn Power Factor Unit = null

Max Demand Conn Current

Max Demand Conn Current is calculated using Connection Voltage data (Voltage Type, Project Voltage) and Max Demand Conn Apparent Power.

Max Demand Conn Current has a unit value of Amp.

Equations for Max Demand Conn Current attributes are:

If Voltage Type = S then
Max Demand Conn Current = (Max Demand Conn Apparent Power * 1000) / Project Voltage

If Voltage Type = L then
Max Demand Conn Current = (Max Demand Conn Apparent Power * 1000) / Project Voltage

If Voltage Type = T, TN then
Max Demand Conn Current = (Max Demand Conn Apparent Power * 1000) / (Project Voltage * 3)

If Voltage Type = DC then
Max Demand Conn Current = (Max Demand Conn Power * 1000) / Project Voltage

Note:
In this case Max Demand Conn Apparent Power = Max Demand Conn Power.