Nameplate Connected Power

  • Last UpdatedNov 12, 2024
  • 2 minute read

Nameplate Connected Power

  • Nameplate Connected Power has a unit value of kW.

  • Nameplate Connected Power is the total active power for all fed equipment tags.

  • Nameplate Connected Power is derived from Nameplate Power.

The equation for Nameplate Connected Power is:

Nameplate Connected Power = Σ Nameplate Electrical Power

Nameplate Connected Reactive Power

Nameplate Connected Reactive Power is the reactive power passing through a tag (Supply Tag).

  • Nameplate Connected Reactive Power has a unit value of kVAr.

  • Nameplate Connected Reactive Power can have a positive or negative value. If positive, the associated power factor unit = LAG and if negative, the associated power factor unit = LEAD.

  • Nameplate Connected Power is the total reactive power for all fed equipment tags.

The equation for Nameplate Connected Reactive Power attributes is:

Nameplate Connected Reactive Power = Σ Nameplate Reactive Power

Nameplate Connected Apparent Power

Nameplate Connected Apparent Power is calculated using Nameplate Connected Active Power and Nameplate Connected Reactive Power.

  • Nameplate Connected Apparent Power has a unit value of kVA.

The equation for Nameplate Connected Apparent Power is:

Nameplate Connected Apparent Power = √ (Nameplate Connected Power2 + Nameplate Connected Reactive Power2)

Nameplate Connected Power Factor

  • Nameplate Connected Power Factor is calculated using Nameplate Connected Active Power and Nameplate Connected Apparent Power.

  • Nameplate Connected Power Factor has a unit value between 0 and 1.

The equation for Nameplate Connected Power Factor is:

Nameplate Connected Power Factor = Nameplate Connected Power / Nameplate Connected Apparent Power

Equations for Nameplate Connected Power Factor Unit attributes are:

If Nameplate Connected Reactive Power value is positive then Nameplate Connected Power Factor Unit = LAG

If Nameplate Connected Reactive Power value is negative then Nameplate Connected Power Factor Unit = LEAD

If Nameplate Connected Reactive Power value = 0 then Nameplate Connected Power Factor Unit = null

Nameplate Connected Current

  • Nameplate Connected Current is calculated using Connection Voltage data (Voltage Type, Project Voltage) and Nameplate Connected Apparent Power.

  • Nameplate Connected Current has a unit value of Amp.

Equations for Nameplate Connected Current attributes are:

If Voltage Type = S then
Nameplate Connected Current = (Nameplate Connected Apparent Power * 1000) / Project Voltage

If Voltage Type = L then
Nameplate Connected Current = (Nameplate Connected Apparent Power * 1000) / Project Voltage

If Voltage Type = T, TN then
Nameplate Connected Current = (Nameplate Connected Apparent Power * 1000) / (Project Voltage * 3)

If Voltage Type = DC then
Nameplate Connected Current = (Nameplate Connected Power * 1000) / Project Voltage

Note:
In this case Nameplate Connected Apparent Power = Nameplate Connected Power.