Nameplate Connected Power
- Last UpdatedNov 12, 2024
- 2 minute read
Nameplate Connected Power
-
Nameplate Connected Power has a unit value of kW.
-
Nameplate Connected Power is the total active power for all fed equipment tags.
-
Nameplate Connected Power is derived from Nameplate Power.
The equation for Nameplate Connected Power is:
Nameplate Connected Power = Σ Nameplate Electrical Power
Nameplate Connected Reactive Power
Nameplate Connected Reactive Power is the reactive power passing through a tag (Supply Tag).
-
Nameplate Connected Reactive Power has a unit value of kVAr.
-
Nameplate Connected Reactive Power can have a positive or negative value. If positive, the associated power factor unit = LAG and if negative, the associated power factor unit = LEAD.
-
Nameplate Connected Power is the total reactive power for all fed equipment tags.
The equation for Nameplate Connected Reactive Power attributes is:
Nameplate Connected Reactive Power = Σ Nameplate Reactive Power
Nameplate Connected Apparent Power
Nameplate Connected Apparent Power is calculated using Nameplate Connected Active Power and Nameplate Connected Reactive Power.
-
Nameplate Connected Apparent Power has a unit value of kVA.
The equation for Nameplate Connected Apparent Power is:
Nameplate Connected Apparent Power = √ (Nameplate Connected Power2 + Nameplate Connected Reactive Power2)
Nameplate Connected Power Factor
-
Nameplate Connected Power Factor is calculated using Nameplate Connected Active Power and Nameplate Connected Apparent Power.
-
Nameplate Connected Power Factor has a unit value between 0 and 1.
The equation for Nameplate Connected Power Factor is:
Nameplate Connected Power Factor = Nameplate Connected Power / Nameplate Connected Apparent Power
Equations for Nameplate Connected Power Factor Unit attributes are:
If Nameplate Connected Reactive Power value is positive then Nameplate Connected Power Factor Unit = LAG
If Nameplate Connected Reactive Power value is negative then Nameplate Connected Power Factor Unit = LEAD
If Nameplate Connected Reactive Power value = 0 then Nameplate Connected Power Factor Unit = null
Nameplate Connected Current
-
Nameplate Connected Current is calculated using Connection Voltage data (Voltage Type, Project Voltage) and Nameplate Connected Apparent Power.
-
Nameplate Connected Current has a unit value of Amp.
Equations for Nameplate Connected Current attributes are:
If Voltage Type = S then
Nameplate Connected Current = (Nameplate Connected Apparent Power * 1000) / Project
Voltage
If Voltage Type = L then
Nameplate Connected Current = (Nameplate Connected Apparent Power * 1000) / Project
Voltage
If Voltage Type = T, TN then
Nameplate Connected Current = (Nameplate Connected Apparent Power * 1000) / (Project
Voltage * 3)
If Voltage Type = DC then
Nameplate Connected Current = (Nameplate Connected Power * 1000) / Project Voltage
Note:
In this case Nameplate Connected Apparent Power = Nameplate Connected Power.