This is the combination of Continuous, Intermittent and Standby absorbed power where Diversity factor is ignored:

Total No DF Conn Power

  • Total No DF Conn Power has a unit value of kW.

  • Total No DF Conn Power is derived from the value of the Utilization for each fed tag. The utilization values are:

    • Continuous

    • Intermittent

    • Standby

The equation for Total No DF Conn Power attributes is:

Total Conn Power = (Σ Continuous Power + Σ Intermittent Power + Σ Standby Power)

Total Conn No DF Reactive Power

  • Total Conn No DF Reactive Power has a unit value of kVAr.

  • Total No DF Conn Power can have a positive or negative value. If positive, the associated power factor unit = LAG and if negative, the associated power factor unit = LEAD.

The equation for Total No DF Conn Reactive Power is:

Total No DF Conn Reactive Power = (Σ Continuous Reactive Power + Σ Intermittent Reactive Power + Σ Standby Reactive Power)

Total No DF Conn Apparent Power

Total No DF Conn Apparent Power has a unit value of kVA.

The equation for Total No DF Conn Apparent Power is:

Total No DF Conn Apparent Power = √ (Total No DF Conn Power2 + Total No DF Conn Reactive Power2)

Total No DF Conn Power Factor

Total No DF Conn Power Factor is calculated using Total No DF Conn Power and Total No DF Conn Apparent Power.

Total No DF Conn Power Factor has a unit value between 0 and 1.

The equation for Total No DF Conn Power Factor is:

Total No DF Conn Power Factor = Total No DF Conn Power / Total No DF Conn Apparent Power

Equations for Total No DF Conn Power Factor Unit attributes are:

If Total No DF Conn Power value is positive then Total No DF Conn Power Factor Unit = LAG

If Total No DF Conn Power value is negative then Total No DF Conn Power Factor Unit = LEAD

If Total No DF Conn Power value = 0 then Total No DF Conn Power Factor Unit = null

Total No DF Conn Current

Total No DF Conn Current is calculated using Connection Voltage data (Voltage Type, Project Voltage) and Total No DF Conn Apparent Power.

Total No DF Conn Current has a unit value of Amp.

Equations for Total No DF Conn Current attributes are:

If Voltage Type = S then
Total No DF Conn Current = (Total No DF Conn Apparent Power * 1000) / Project Voltage

If Voltage Type = L then
Total No DF Conn Current = (Total No DF Conn Apparent Power * 1000) / Project Voltage

If Voltage Type = T, TN then
Total No DF Conn Current = (Total No DF Conn Apparent Power * 1000) / (Project Voltage * 3)

If Voltage Type = DC then
Total No DF Conn Current = (Total No DF Conn Power * 1000) / Project Voltage

Note:
In this case Total No DF Conn Apparent Power = Total No DF Conn Power.