Total Connected Power

  • Last UpdatedApr 08, 2024
  • 2 minute read

This is the combination of Continuous, Intermittent and Standby absorbed power.

Total Conn Power

  • Total Conn Power has a unit value of kW.

  • Fed tag Diversity has a unit of ratio.

  • Total Conn Power is the summation of the following Utilizations for each fed tag. The utilization values are:

    • Continuous

    • Intermittent

    • Standby

The equation for Total Conn Power is:

Total Conn Power = (Σ Continuous Power + Σ Intermittent Power + Σ Standby Power)

Total Conn Reactive Power

  • Total Conn Reactive Power has a unit value of kVAr.

  • Total Conn Reactive Power can have a positive or negative value. If positive, the associated power factor unit = LAG and if negative, the associated power factor unit = LEAD.

  • Fed tag Diversity has a unit of ratio.

The equation for Total Conn Reactive Power is:

Total Conn Reactive Power = (Σ Continuous Reactive Power + Σ Intermittent Reactive Power + Σ Standby Reactive Power)

Total Conn Apparent Power

Total Conn Apparent Power has a unit value of kVA.

The equation for Total Conn Apparent Power is:

Total Conn Apparent Power = √ (Total Conn Power2 + Total Conn Reactive Power2)

Total Conn Power Factor

Total Conn Power Factor is calculated using Total Conn Power and Total Conn Apparent Power

Total Conn Power Factor has a unit value between 0 and 1.

The equation for Total Conn Power Factor is:

Total Conn Power Factor = Total Conn Power / Total Conn Apparent Power

Equations for Total Conn Power Factor Unit attributes are:

If Total Conn Reactive Power value is positive then Total Conn Power Factor Unit = LAG

If Total Conn Reactive Power value is negative then Total Conn Power Factor Unit = LEAD

If Total Conn Reactive Power value = 0 then Total Conn Power Factor Unit = null

Total Conn Current

Total Conn Current is calculated using Connection Voltage data (Voltage Type, Project Voltage) and Total Conn Apparent Power.

Total Conn Current has a unit value of Amp.

Equations for Total Conn Current attributes are:

If Voltage Type = S then
Total Conn Current = (Total Conn Apparent Power * 1000) / Project Voltage

If Voltage Type = L then
Total Conn Current = (Total Conn Apparent Power * 1000) / Project Voltage

If Voltage Type = T, TN then
Total Conn Current = (Total Conn Apparent Power * 1000) / (Project Voltage * 3)

If Voltage Type = DC then
Total Conn Current = (Total Conn Power * 1000) / Project Voltage

Note:
In this case Total Conn Apparent Power = Total Conn Power.