HVBRCO flat oval requirements
- Last UpdatedAug 25, 2025
- 4 minute read
This topic describes the specification requirements for branch connector (HVBRCO) sub components positioned on flat oval owning ducting.
Parameter description requirements
-
Parameter #1 = Width of branch
-
Parameter #2 = Height of branch
-
Parameter #4 = Width of owning arrive
-
Parameter #5 = Height of owning arrive
Data set requirements
For information about data set requirements that apply for all flat oval components, refer to Flat oval component requirements.
The following requirements for when the Owner Shape is RECT, are in addition to the data references that are created for parameters.
|
KEY |
Type |
Description |
Default ( /Expression **) |
|
SHAP |
Expression |
Duct shape |
‘OVAL’ |
|
SHAB |
Expression |
Shape of branch connection |
‘OVAL’ or ‘CIRC’ |
|
AARR |
Distance |
Width of arrive |
PARA[4 ] |
|
BARR |
Distance |
Height of arrive |
PARA[5 ] |
|
ALEA |
Distance |
Width of leave |
0 |
|
BLEA |
Distance |
Height of leave |
0 |
|
ABRA |
Distance |
Width of branch |
PARA[1 ] |
|
BBRA |
Distance |
Height of branch |
PARA[2 ] or 0 if CIRC |
|
LENG |
Distance |
Length of subcomponent in line of duct |
Not available |
** Where the Default value is set to a parameter, the Expression value must be set to the same parameter. This is applicable for all component types.
The following requirements for when the Owner Shape is CIRC, are in addition to the data references that are created for parameters.
|
KEY |
Type |
Description |
Default ( /Expression **) |
|
SHAP |
Expression |
Duct shape |
‘OVAL’ |
|
SHAB |
Expression |
Shape of branch connection |
Not available |
|
AARR |
Distance |
Width of arrive |
PARA[4 ] |
|
BARR |
Distance |
Height of arrive |
0 |
|
ALEA |
Distance |
Width of leave |
0 |
|
BLEA |
Distance |
Height of leave |
0 |
|
ABRA |
Distance |
Width of branch |
PARA[1 ] |
|
BBRA |
Distance |
Height of branch |
PARA[2 ] or 0 if CIRC |
** Where the Default value is set to a parameter, the Expression value must be set to the same parameter. This is applicable for all component types.
P-point requirements
The following P-points are required for branch connectors positioned on flat oval owning ducting.
Because branch connectors positioned on flat oval owning ducting are sub components, without an arrive or leave, the P-points are different from inline components. The orientation of the P-points and the geometry must follow the examples in this topic.
-
P9 defines the position and orientation of the branch connector on the surface of the owning duct, and must be on the X axis, with a direction of X, and positioned at the intersection of the owning duct.
-
P9 can be any P-Point type, but PTAX is the simplest option because it is positioned on the X axis and directed to X.
-
Axis Direction (PAXI) must be X.
-
PZ Axis (PZAXI) must be Y.
In most cases, P9 is set as shown in the following graphic:

-
-
P3 is used to define the branch connection size and shape, and to position the branch connector in the Model module.
-
P3 must be positioned at the branch connection point, in the direction the attached branch leave will be.
-
P3 can be any P-point type.
-
Connection Type (PCON) must be CIRC or OVAL.
-
For flat oval, Bore (PBOR) must be (RPRO ABRA +RPRO BBRA).
-
For circular, Bore (PBOR) must be (RPRO ABRA).
-
For flat oval, Point Width (PWID) must be (RPRO ABRA +RPRO BBRA).
-
For circular, Point Width (PWID) must be (RPRO ABRA).
-
PDShape attribute must be CIRC or OVAL.
-
AllAngle attribute must be 1 or 180 and match the shape of the connecting duct.
PDShape and AllAngle attributes cannot be set on the Model View form, they must be manually set on the Attributes form or the Command Window.
In most cases, P3 is set as shown in the following graphic:

-
All sub components that are located on the surface of flat oval ducting require P-points P61–P64. These are used by the HVAC application to control the placement on inline components, and on implied ducting components.
P61–P64 must be defined according to the following:
-
The P-points must be on the same Y-Z plane as P-point P9.
-
The P-points must have Direction set to -X.
-
The P-point type is not required, but PTMI is recommended because it allows the required position and Axis Direction to be set easily.
The order of the P-points and PAXI setting do not affect how the components work, but it is good practice to be consistent when building the catalogue.
With P9 having a PAXI of 'X', P61–P64 will be on the same Y-Z plane, with a PAXI of '-X', and the P-points arranged as shown in the following graphic:

In most cases, P61 for example, is set as shown in the following graphic:

Specification requirements
The following specification headings are required:
-
Type (TYPE)
-
Owner Shape (OSHA)
-
Shape of Branch Connector (SHAB)
-
Owner Width (OWID)
-
Owner Height (OHEI)= 0
-
Specific Type (STYP)
For rows which have Owner Shape set to OVAL, the Owner Width is set to 0 and Owner Height is set to the height of the flat oval duct. This restricts the branch connector to a specific size of main.