Automatic request
- Last UpdatedApr 24, 2025
- 1 minute read
An automatic request to upload the completed tickets is sent to the Flow Computer when the Batch Start Indicator Analog or the Batch Split Indicator Analog increments in value. When either the Batch Start Indicator Analog point that the Administrator has defined or the Batch Split Indicator Analog increments, the difference in the values will determine how many completed tickets will be requested.
For example, if a communications outage occurs when the Batch Start Indicator Analog has a current value of 5 and the Batch Split Indicator Analog has a current value of 8, those values will be saved into the database. When communications are restored, the Batch Start Indicator Analog and Batch Split Indicator Analog will update to the telemetered values. In our example, assume the Batch Start Indicator Analog is 8 and the Batch Split Indicator Analog is 10. This would result in (8-5) + (10-8) = 5 completed tickets being requested from the Flow Computer.