AVEVA Pipeline Operations for Liquids

Flow Network Shutdown with Delay Timer in Effect

  • Last UpdatedApr 24, 2025
  • 1 minute read

For each Flow Network, The Controller can configure one or both types of delay timers:

  • Uncommanded Shutdown Delay For Closed State: the system aborts the shutdown sequence if the valve exits the closed state before a configured number of seconds expire.

  • Uncommanded Shutdown Delay For Closing State: the system aborts the shutdown sequence if the valve exits the closing state before a configured number of seconds expire.

    Note: While a Closing delay timer may be 10 seconds long, if a valve moves, (for example, from a CLOSING state to a CLOSED state after 5 seconds), there may exist a Closed delay timer of 20 seconds. In such a situation, you would then have 25 seconds to remedy the situation. If, for example, you manage to move the valve out of the CLOSED state within 15 seconds, no shutdown occurs.

Delay Timer in Effect—Possible to prevent a Shutdown.