Flow Network Protected Location alarm and event messages
- Last UpdatedApr 24, 2025
- 1 minute read
|
# |
Message |
Alarm or Event |
Notes |
|---|---|---|---|
|
1 |
Protected Location NameOfProtectedLocation is no longer in violation of any of its High Mode conditions. |
Both |
Occurs when no violations are detected. The system generates the message regardless of whether a Flow Network is in High mode. |
|
2 |
In violation but not in High Mode. |
Event |
|
|
3 |
In High Mode violation. |
Both |
Generated if the Flow Network where the violation is found is in High mode. |
|
4 |
Table.Point (Condition): Reading |
Generated immediately after either message #2 or #3. One message will appear for every condition in violation. Where:
|
|
|
5 |
Upstream station(s) that will be shut down: Y (sequence: Y_ACTIONSEQUENCE). or, Upstream station(s) that will be shut down: Y (No sequence configured). |
Both |
Generated after message(s) #4 if the application locates upstream stations in violation. The system generates one message for each station in violation. Y = The name of the protectedLocation record attached to the upstream station (Flow Network). Y_ACTIONSEQUENCE = the name of the action sequence configured on the Y Protected Location, if it exists. |