Configure the Reflex (reflex) record for Action Sequence alarming
- Last UpdatedApr 24, 2025
- 2 minute read
Action Sequence alarming of the Reflex (reflex) record is configured using the reflex Row Edit dialog.
To configure the reflex record for Action Sequence alarming
-
Expand the reflex Table Edit from the Advanced Database Editor (ADE), and double-click the desired record to open.
The reflex Row Edit dialog appears.

-
(Optional) In the Point Class field, select (...) to configure the reflex point class.
-
(Optional) In the Point SubClass field, select (...) to configure the reflex point subclass.
-
Select the Alarming tab.
The Alarming tab appears.

-
(Optional) Select Enable Start Alarm to raise an alarm when the reflex is triggered.
-
(Optional) Select Enable Expiry Alarm to raise an alarm when reflex timer has counted down to (0).
-
(Optional) Select Enable Warning Alarm to raise an alarm and event when the countdown timer passes the Warning Alarm Threshold in seconds value.
-
(Optional) If Enable Warning Alarm is selected, in the Warning Alarm Threshold in seconds field, enter the time (in seconds) before the countdown expires.
Note: If Enable Warning Alarm is selected, the Warning Alarm Threshold in seconds value cannot be set to zero (0).