AVEVA Pipeline Operations for Liquids

Configure the Reflex (reflex) record for Action Sequence alarming

Configure the Reflex (reflex) record for Action Sequence alarming

  • Last UpdatedApr 24, 2025
  • 2 minute read

Action Sequence alarming of the Reflex (reflex) record is configured using the reflex Row Edit dialog.

To configure the reflex record for Action Sequence alarming

  1. Expand the reflex Table Edit from the Advanced Database Editor (ADE), and double-click the desired record to open.

    The reflex Row Edit dialog appears.

    Embedded Image (65% Scaling) (LIVE)

  2. (Optional) In the Point Class field, select (...) to configure the reflex point class.

  3. (Optional) In the Point SubClass field, select (...) to configure the reflex point subclass.

  4. Select the Alarming tab.

    The Alarming tab appears.

  5. (Optional) Select Enable Start Alarm to raise an alarm when the reflex is triggered.

  6. (Optional) Select Enable Expiry Alarm to raise an alarm when reflex timer has counted down to (0).

  7. (Optional) Select Enable Warning Alarm to raise an alarm and event when the countdown timer passes the Warning Alarm Threshold in seconds value.

  8. (Optional) If Enable Warning Alarm is selected, in the Warning Alarm Threshold in seconds field, enter the time (in seconds) before the countdown expires.

    Note: If Enable Warning Alarm is selected, the Warning Alarm Threshold in seconds value cannot be set to zero (0).