Open the Action Sequence Step Control dialog
- Last UpdatedApr 24, 2025
- 2 minute read
To open the Action Sequence Step Control dialog
-
On the Action Sequence Step Summary window, select the row header for any sequence step.
One of the Action Sequence Step Control dialogs is displayed, depending on the type of point selected.
The table below lists the action items and fields on the Action Sequence Step Control dialog.
|
Fields |
Description |
|---|---|
|
Name |
The configured name of the sequence step. |
|
State |
The current state of the step. For a list of possible states, see Opening the Action Sequence Control Dialog Box. |
|
Type |
The step type. For an explanation of possible step types, see Opening the Action Sequence Control Dialog Box. |
|
Command |
The command that will be executed on the point. This field is only visible for the following types of points:
|
|
Value |
The value that the point will be set to. This field is only visible if an analog point has been defined by the step. |
|
Target State |
The target state for the point to reach for the command to have been considered successful. This field is only visible if a status, multistate, pump or valve point is defined by the step. |
|
Deadband |
How close to the configured value an analog point must get for it to be considered successful. This field is only visible if an analog point is defined by the step. |
|
Timeout |
The maximum duration that a step can take to reach its desired state before being declared a failure. If the point is a Wait type point, this field indicates how long the step will wait before proceeding. |
|
Retry Attempts |
For a Set type step, if a failure occurs, the Action Sequence will re-execute the command the specified number of times before the step is considered a failure. |
|
Step Inhibited |
A checkbox indicating if the step is inhibited. This value can be toggled by clicking on it when the Action Sequence is not executing. If the Administrator has inhibited the step, the Step Inhibited checkbox will be unavailable for edit. |
|
Start at Step |
Starts the action sequence at this step. There are a few things that will disable the Start at Step button:
|
|
Dismiss |
Close the Action Sequence Step Control Panel dialog. |