Understand valve Line Blockage events
- Last UpdatedApr 24, 2025
- 2 minute read
The following table lists events that are generated by Line Blockage related to valves. If a valve has a status or multistate configured as its telemetry source, alarms and events will be generated against this point rather than the valve record.
|
Event Text |
Description |
Inhibit Type |
|---|---|---|
|
Flow Path flag added to valve. |
An event that occurs whenever a change in topography results in the Flow Path flag on a valve being added. This addition indicates that the valve's closure would result in a pump blockage. |
Off-normal inhibit |
|
Flow Path flag removed from valve. |
An event that occurs whenever a change in topography results in the Flow Path flag on a valve being removed. This removal indicates that the valve's closure would no longer result in a pump blockage. |
Off-normal inhibit |
|
Logic Excluded Mode Timer started. Logic state will revert in <minutes> minutes. |
A valve's logic mode has been changed out of In Service with a timer configured. After the indicated duration, the logic mode will revert to In Service. |
Return-to-normal inhibit |
|
Logic Excluded Mode Timer reset. Logic state will revert in <minutes> minutes. |
A valve's logic mode timer was reset. The countdown to when the logic mode will be reverted is restarted to the configured duration. |
Return-to-normal inhibit |
|
Logic Excluded Mode Timer canceled. |
A timer to automatically revert the logic mode was canceled. |
Return-to-normal inhibit |
|
Logic Excluded Mode Timer expired. Reverting to 'In Service'. |
A timer expired and the logic mode reverted back to In Service. |
Return-to-normal inhibit |
|
An override was performed for <type> by <username> at <location>. |
An event that is generated when a Controller overrides a warning when executing a command on a valve. |
Off-Normal Event Inhibit |
|
Shut Down sequence automatically executed for <device names> due to command โ<command>โ on valve <valve name>. |
A shut down action sequence was initiated due to an authorized valve command that resulted in a Line Blockage (Close, In Service, Out Of Service Close). This event is attached to the actionSequence record that was activated. |
Off-Normal Inhibit |