AVEVA Pipeline Operations for Liquids

Understand the tank message set

  • Last UpdatedApr 24, 2025
  • 3 minute read

A default message set is provided with each AVEVA Pipeline Operations for Liquids release for tanks. However, existing message sets can be used by a tank record. For full functionality, a message set must have 24 entries to provide support for all tank alarms. The default message set from the file LMS.message.l. Each row of the message set is applied to a condition for the tank record. The message sets used by the Tanking application are described as follows:

Number

Message Set Use

Description

0

Return-to-Normal alarms

Any Return-to-Normal alarm generated by a tank from a previous alarm state will generate an alarm based on this configuration.

1

High (Hi) alarms

A tank level exceeding the configured High Limit will generate an alarm based on this configuration.

2

Low (Lo) alarms

A tank level falling below the configured Low Limit will generate an alarm based on this configuration.

3

Deviation alarms

An idle tank exceeding the maximum positive or negative creep deviation will generate an alarm based on this configuration.

4

HighHigh (HiHi) alarms

A tank level exceeding the configured HighHigh Limit will generate an alarm based on this configuration.

5

LowLow (LoLo) alarms

A tank level falling below the configured LowLow Limit will generate an alarm based on this configuration.

6

Instrument Failure High alarms

A tank reading from a field device that exceeds the Maximum Instrument Value or the Maximum Physical Level, will generate an alarm based on this configuration.

7

Instrument Failure Low alarms

A tank reading from a field device that is negative or below the Minimum Instrument Value, will generate an alarm based on this configuration.

8

Rate of Change (ROC) alarms

A tank flow rate exceeding the specified filling or emptying ROC limits will generate an alarm.

9

Flat-line alarms

A tank that is detected to have flat-lined will generate an alarm based on this configuration. This alarm is specific to AVEVA Pipeline Operations for Liquids.

10

Fill/Empty Warning alarms

A tank that triggers the fill/empty warning time threshold when filling or emptying will generate an alarm based on this configuration.

11

Gross Standard Volume (GSV) Target Volume alarms

The message configuration has been deprecated and replaced with Countdown.

12

Gross Observed Volume (GOV) Target Volume alarms

The message configuration has been deprecated and replaced with Countdown.

13

User High (Hi) alarms

A tank level exceeding the configured Maximum User High Level will generate an alarm based on this configuration.

14

User Low (Lo) alarms

A tank level falling below the configured Minimum User Low Level will generate an alarm based on this configuration.

15

GSV Warning Time alarms

The message configuration has been deprecated and replaced with Countdown.

16

GOV Warning Time alarms

The message configuration has been deprecated and replaced with Countdown.

17

Bad Level alarms

A tank that receives a level reading that is not within its configured Strapping table will generate an alarm based on this configuration.

18

Bad Telemetered Volume alarms

A tank that receives a volume reading that is not within its configured Strapping table will generate an alarm based on this configuration.

19

Service Response Bad alarms

A tank that receives a failure from a supporting Tanking Application Service will generate an alarm based on this configuration.

20

Service Response Good alarms

A tank that receives a success from a supporting Tanking Application Service after a failure will generate an alarm based on this configuration.

21

Normal Empty alarm

A tank level falling below the configured Normal Empty Level will generate an alarm based on this configuration.

22

Normal Fill alarm

A tank level exceeding the configured Normal Fill Level will generate an alarm based on this configuration.

23

Invalid Level or Limit Configuration

If a configured level or alarm limit exceeds the Maximum Strap Level entered into the Strapping table, an alarm and event will be generated to inform you about the invalid configuration.