Select the Pumpstation record analog points to calculate power usage efficiency
- Last UpdatedApr 24, 2025
- 2 minute read
The first five fields shown on the Station Efficiency tab are used to enter or select the analog points providing the information required for the power usage efficiency calculation.
To select the analog points to calculate power usage efficiency
-
Click (…) to open the analog Select dialog to view the analog points that are available for selection.
The analog Select dialog appears.

-
Select (…) for any given filter to view the options that are available for selection.
Note: You can filter by name or by the options outlined in the Filters section.
For more information, see Station Efficiency .
The following table details the fields on the Station Efficiency tab of the pumpstation Row Edit dialog.
|
Field |
Notes |
|---|---|
|
Kilowatt Demand |
Click (…) and select the name of the analog record from the analog Select dialog. Note: You can also filter by name. This field is used both by Station Efficiency and by the Pump Power Management module as the current power demand for the pumpstation. If this field is not configured, station efficiency will not be calculated, but the pump validation module will assume that the station power is to be calculated from the sum of the running pumps at the pumpstation. |
|
Discharge Pressure |
Click (…) and select the name of the analog record from the analog Select dialog. Note: You can also filter by name. If Case Pressure is configured, this is not required. |
|
Suction Pressure |
Click the (…) and select the name of the analog record from the analog Select dialog. Note: You can also filter by name. |
|
Throttle Pressure |
Click the (…) and select the name of the analog record from the analog Select dialog. Note: You can also filter by name. If Case Pressure is configured, this is not required. |
|
Case Pressure |
Click (…) and select the name of the analog record from the analog Select dialog. Note: You can also filter by name. |
|
Node |
Used to enter the name of the record in the node table that provides the flow rate. In order for this to be successful, you must also have a Batch Tracking record configured. |