Calculate volumetric change for meter type devices
- Last UpdatedApr 24, 2025
- 2 minute read
To calculate volumetric change for meter type devices
-
Find out the current volume counter and related information from the metering device.
Related information includes timestamp, rollover for counter, and data quality flags.
-
Adjust the current volume counter if Meter Extrapolation is enabled.
For more information, see Understand meter extrapolation for further explanation.
-
Check the usability of the device volume.
For more information, see Determine the usability of device volumes. If it is not usable, a zero volume delta is saved as the most recent delta and volume calculation for the device is done.
-
Determine delta volume (usability check has been passed).
-
Delta volume is current volume counter minus previous volume counter, allowing for rollover:


-
-
An alarm is raised if delta volume exceeds 10% of the rollover value.
The current volume counter is saved so that it can be used as the previous volume counter on the next processing.
-
Save the delta volume. An array of the past 30 minutes of volume reading is maintained for each device.
-
Check the device as a source of imbalance.
For more information, see Flag the input device as a leak location.