Understand Anomaly Detect Batch Tracking Compiler (BTC) attributes
- Last UpdatedApr 24, 2025
- 4 minute read
The table below shows the Anomaly Detect (adetect) record Batch Tracking Compiler (BTC) attributes.
|
Attribute Name |
Description |
Required |
|---|---|---|
|
ADETECT |
Record name. |
Yes. |
|
ADETECTTYPE |
The anomaly detect type can be set to one of the following options: • Unspecified • Launcher • Detector • Receiver |
No. Defaults to Unspecified. |
|
TRIGGERPOINT |
Two values are present:
|
No. |
|
GROUP |
Group. |
No. If not specified, group will be inherited from pipeline record. |
|
DESCRIPTION |
Description. |
No. |
|
SEVERITY |
Severity of alarms issued against the detect record. The severity can be set to one of the following states:
|
No. Defaults to lowest severity possible. |
|
INH |
This field can be set to one or two states:
|
No. |
|
VDEADBAND |
Two values are present:
Note: VDEADBAND applies when the Anomaly Detect Type is set to Unspecified. |
No. If not present both values default to zero (0). Zero disables this check. |
|
AUTOLAUNCHRECEIVER |
The point name of adetect of type Receiver. |
No. If not present the value will be blank. |
|
VNORMDETECT |
Two values are present: Upstream normal detection volume—positive value. The value should be less than the one for VELDETECT if specified and not exceed the segment linepack upstream of the adetect. Downstream normal detection volume—negative value. The absolute value should be less than the one for VELDETECT if specified and not exceed the segment linepack downstream of the adetect. Note: VNORMDETECT only applies when the Anomaly Detect Type is set to Detector or Receiver. |
No. If not present, both values default to zero (0). Zero disables this check. |
|
VELDETECT |
Two values are present: Upstream early detection volume—positive value. The value should be greater than the one for VNORMDETECT if specified and not exceed the segment linepack upstream of the adetect. Downstream late detection volume—negative value. The absolute value should be greater than the one for VNORMDETECT if specified and not exceed the segment linepack downstream of the adetect. Note: VELDETECT only applies when the Anomaly Detect Type is set to Detector or Receiver. |
No. If not present, both values default to zero (0). Zero disables this check. |
|
VNORMDETECTINH |
This field can be set to one or two states:
|
No. Default is False. |
|
VELDETECTINH |
This field can be set to one or two states:
|
No. Default is False. |
|
V2ELDETECTINH |
This field can be set to one or two states:
|
No. Default is False. |
|
MISSETAINH |
This field can be set to one or two states:
|
No. Default is False. |
|
MISSSIGNALINH |
This field can be set to one or two states:
|
No. Default is False. |
|
TDEADBAND |
Early time limit. If anomaly is not predicted to have arrived yet and estimated time of arrival for the anomaly is greater than this value, detection is early. |
No. Default is zero (0). Zero disables this check. |
|
EVTINH |
This field can be set to one or two states:
|
No. Default is False. |
|
ALMINH |
This field can be set to one or two states:
|
No. Default is False. |
|
ANMTYPE |
Type of anomaly to detect. |
Yes. If not present an anomaly cannot be created to mark the early or late detection. |
|
RECEIVEINH |
This field can be set to one or two states:
|
No. Default is False. |
|
LAUNCHINH |
This field can be set to one or two states: • True • False If True, the alarm is inhibited when an anomaly is launched. |
No. Default is False. |
|
BMSG |
This is the standard RealTime database (RTDB) field flag.bmsg. If ADETECTTYPE is set to Unspecified (for basic anomaly detection deadbands), use adetect. If ADETECTTYPE is set to Launcher, Detector, or Receiver (for enhanced anomaly detection deadbands), use adetectEnhanced. |
No. |