Configure the Flow Rates tab of the Pressmon Row Edit dialog
- Last UpdatedApr 24, 2025
- 2 minute read

The following table provides a description of the items on the Flow Rates tab in the pressmon Row Edit dialog.
|
Items |
Description |
|---|---|
|
Flowpath |
Click (...) to select the path of a point and obtain the flow rate. Note: The Table field is limited to analog, rate, BatchXfer, or virtualflowcomputer. The Field field is limited to curval (analog table), GSflow (batchXfer table), curate (rate table), and flowrate (virtualflowcomputer table). The field must be of type float or double and must represent a flow rate. |
|
+DB1 |
Enter a positive deadband value. In cases where the actual flow rate is greater than the estimated flow rate, Pressmon uses this deadband when comparing the estimated and actual flow rates. |
|
-DB1 |
Enter a negative deadband value. In cases where the actual flow rate is less than the estimated flow rate, Pressmon uses this deadband when comparing the estimated and actual flow rate. |
|
+DB2 |
Enter a positive deadband value. Pressmon uses this deadband when comparing the estimated and actual flow rates. This deadband is used when the actual flow rate crosses the first deadband (+DB1) in the previous iteration, and the actual flow rate is greater than the estimated flow rate. |
|
-DB2 |
Enter a positive deadband value. Pressmon uses this deadband when comparing the estimated and actual flow rates. This deadband is used when the actual flow rate crosses the first deadband (-DB1) in the previous iteration, and the actual flow rate is less than the estimated flow rate. |
|
Inhibited |
Select the checkbox to exclude the flowpath rate from the deviation calculations. |