AVEVA Pipeline Operations for Liquids

Understand Interface Detect record Batch Tracking Compiler (BTC) attributes

Understand Interface Detect record Batch Tracking Compiler (BTC) attributes

  • Last UpdatedApr 24, 2025
  • 2 minute read

The table below shows the detect record’s Batch Tracking Compiler (BTC) attributes.

Attribute Name

Description

Required

DETECT

Record name.

Yes.

GROUP

Group.

No. If not specified, group will be inherited from the pipeline record.

DESCRIPTION

Description.

No.

SEVERITY

Severity of alarms issued against the detect record.

  • LOW

  • MEDIUM

  • HIGH

No. Defaults to lowest severity possible.

TICKET

TRUE or FALSE. If true, a Ticket Start or Ticket Split command is issued to the associated Batch Transfer (batchxfer) when an interface is detected.

No.

INH

TRUE or FALSE. If true, processing of record is inhibited.

No.

CORRECTED

TRUE or FALSE. If true, density readings are corrected for temperature.

No.

ANALOG

Name of analog record polling the detection device.

Yes.

ANATYPE

Type of detection device, DENSITY or VELOCITY.

No. Default is Velocity.

SDDEADBAND

Minimum change in device reading for interface detection to be considered.

No.

VOLDEADBAND

Volume zone upstream and downstream of the detector location. If the interface to a detected batch is tracked as being outside of this zone detection is early or late.

No. Default is zero (0). A zero value means that a detected interface will always be flagged as early or late.

EVTINH

TRUE or FALSE. If true, alarm events are inhibited.

No. Default is false.

ALMINH

TRUE or FALSE. If true, alarms are inhibited.

No. Default is false.

CLREVTINH

TRUE or FALSE. If true, Return-to-Normal (RTN) events are inhibited.

No. Default is false.

CLRALMINH

TRUE or FALSE. If true, Return-to-Normal alarms are inhibited.

No. Default is false.

BATCHXFER

Name of the batchxfer associated with the device. If a batchxfer is present, the batchxfer schedule will be checked for detected batches.

No.

DENSEL

Source of density for next batch to detect. If the density is set to SCHEDULE, density comes from the batch record itself. If set to ENTERED, density is a value manually entered in the detect record.

No. Default is Schedule.