Define Return-to-Normal Deadband
- Last UpdatedJul 04, 2024
- 3 minute read
The Return-to-Normal Deadband Percentage (or RTN Deadband %) column can be used to specify when the system should return to normal after a deviation alarm. There are two types of limit alarms, the Volume Over Limit alarm and the Volume Short Limit alarm.
Volume Over Limit
After a Volume Over Limit alarm has been raised due to the volume deviation going above the specified value X, the system does not raise a Return-to-Normal (RTN) alarm until the volume deviation reaches or goes below X ´ RTN Deadband %.
Volume Short Limit
After a Volume Short Limit alarm has been raised due to the volume deviation going below the specified value X, the system does not raise a Return-to-Normal alarm until the volume deviation reaches or goes above X ´ RTN Deadband %.
Note: If the RTN Deadband % value is set to 0, the system will not apply any deadband to the limits.
There are three behavioral cases depending on the Alarm Type configured for each term:
Case A: When the Alarm Type is set to Volume
After a Volume Over Limit alarm has been raised due to the volume deviation going above the specified value X, the system does not raise a Return-to-Normal alarm until the volume deviation drops below X ´ RTN Deadband %.
Example 1—If the Over Limit alarm is configured at 200 m³ and the RTN Deadband % is configured at 15%, then:
-
A Volume Over Limit alarm is raised when the volume delta > 200 m³.
-
A RTN alarm is raised when the volume delta £ 30 (calculated as 200 ´ 15%).
Example 2—If the Over Limit alarm is configured at 200 m³ and the RTN Deadband % is configured at 100%, then:
-
A Volume Over Limit alarm is raised when the volume delta > 200 m³.
-
A RTN alarm is raised when the volume delta £ 200 (calculated as 200 ´ 100%).
After a Volume Short Limit alarm has been raised due to the volume deviation going below the specified value X, the system does not raise a Return-to-Normal alarm until the volume deviation goes above X ´ RTN Deadband %.
Example 1—If the Short Limit alarm is configured at -200 m³ and the RTN Deadband % is configured at 15%, then:
-
A Volume Short Limit alarm is raised when the volume delta < -200 m³.
-
A RTN alarm is raised when the volume delta ³ -30 (calculated as -200 ´ 15%).
Example 2—If the Short Limit alarm is configured at 200 m³ and the RTN Deadband % is configured at 100%, then:
-
A Volume Short Limit alarm is raised when the volume delta < -200 m³.
-
A RTN alarm is raised when the volume delta ³ -200 (calculated as -200 ´ 100%).
Case B: When the Alarm Type is set to Flow Percent
The logic explained in Case A applies to the Flow Percent limit.
Example 1—If the Over Limit alarm is configured at 10% and the RTN Deadband % is configured at 15%, then:
-
A Volume Over Limit alarm is raised when the Flow Percent calculated using the volume delta > 10%.
-
A RTN alarm is raised when the Flow Percent £ 1.5% (calculated as 10% ´ 15%).
Example 2—If the Short Limit alarm is configured at -10% and the RTN Deadband % is configured at 15%, then:
-
A Volume Short Limit alarm is raised when the Flow Percent calculated using the volume delta < -10%.
-
A RTN alarm is raised when the Flow Percent ³ -1.5% (calculated as -10% ´ 15%).
Case C: When the Alarm Type is set to Switching
The logic explained in Case A and Case B applies depending on whether the system is using Volume limits or Flow Percent limits.