Access the Interface Detect Control dialog
- Last UpdatedApr 24, 2025
- 3 minute read
Interface detection is controlled through the Interface Detect Control dialog.
To access the Interface Control Detect dialog
-
On the Interface Detect Summary window, select the row header of the desired interface detector (detect) record.

The Interface Detect Control dialog appears.

The following table details the items on the Interface Detect Control dialog.
|
Group Box |
Item |
Description |
Allow Controller Edit |
Detect Table Field |
|---|---|---|---|---|
|
Node |
Name of node where detector is located. |
no |
node |
|
|
Value Type |
The value type indicates the type of measurement.
|
no |
anatype |
|
|
Alarm |
The detect record alarm state can be one of the following options:
|
no |
alm_state |
|
|
Status |
This defines the ability of detect record processing to calculate a threshold. There will be a Check if Batch Tracking is able to calculate a threshold, and the status will be set to Idle if it is not. |
no |
state |
|
|
Current Interface Detection |
Current Batch |
This defines the ID number of the batch currently flowing past. |
no |
curr_batch |
|
Analog Deadband |
This defines the amount of change in the property value reading that must occur to for the batch cut to be declared. |
yes |
sd_deadband |
|
|
Cut Type |
This defines the type of cut to apply to the end of the batch. That is, where to locate the interface in the transmix zone between the current and next batch. The available options are:
|
no |
cut_type |
|
|
Gross Standard Volume (GSV) Deadband |
The deadband in which the batch interface as predicted by Batch Tracking must be within when detected, either upstream or downstream of the detector location, for the prediction to be considered correct. |
yes |
vol_deadband |
|
|
Next Batch |
ID of next batch upstream of the current. |
no |
next_batch |
|
|
Next Density/Gravity |
The property value to use for the next batch, if Density Selection Method configured in the detect Row Edit dialog in Advanced Database Editor (ADE) is Entered. Note: This can be used for either density or sonic velocity types. |
yes |
mandens |
|
|
Previous Missed Detection |
Current Batch |
If an interface passed the detector without detection, this is the ID of the batch forming the downstream side of the interface. |
no |
miss_c_batch |
|
Next Batch |
If an interface passed the detector without detection, this is the ID of the batch forming the upstream side of the interface. |
no |
miss_n_batch |
|
|
Density/Gravity Correction Inhibited |
If selected, and if Value Type is Density/Gravity, the value read from the analog will be corrected for temperature. |
yes |
corrected |
|
|
Monitoring Inhibited |
If selected, detect record is inhibited from processing. |
yes |
inh |
|
|
Auto Ticket Cut |
If selected, and if a batch transfer (batchXfer) is assigned to the detect record, a command to start a new ticket will be issued to the batchXfer when an interface is detected. If the ticket start command fails, a ticket split command will be issued. |
yes |
ticket |