Understand reflex application operational override for timeout
- Last UpdatedApr 24, 2025
- 1 minute read
Third-party applications can override the Timeout (s) value of a reflex record. To set an override value for the Timeout (s) field, the internal actionSequenceCountdownOverride field can be set using any AVEVA Enterprise SCADA Application Programming Interface (API), such as Open Database Connectivity (ODBC) data sources or Business Logic Tiers (BLTs).
To set an override value in a third-party application using a BLT, the Developer can use the Fldput BLT, and input the following parameters.
Note: The override value will only affect the next trigger of the reflex record. As soon as the reflex record has triggered and started counting down, the override value will reset to zero (0) and any future triggers of the reflex record will use the configured Timeout (s) field value.
|
Parameter Name |
Parameter Value |
|---|---|
|
table |
Reflex |
|
key |
<Reflex name> is the name or point number of the reflex record. |
|
field |
actionSequenceCountdownOverride |
|
value |
<override value> is the new timeout override value (in seconds). |
For more information on how to use BLTs in your application, including the Fldput BLT, refer to the RealTime Developer documentation.
For more information on how to work with the Reflex Monitor application for Action Sequences, refer to the AVEVA Pipeline Operations for Liquids Administrator Guide documentation.