Configure System Endpoints
- Last UpdatedJul 04, 2024
- 1 minute read
If reflex records have a Target System configured to execute on a Delegate System, then a System Endpoint record must be configured for each system that could own a trigger record defined on the reflex record. This configuration will allow the Reflex Monitor application to discover the correct system to execute a command on when the Trigger field changes.
Note: If a reflex record is configured to execute on a Delegate System, but no Delegate System is currently configured in the System Endpoint table, then the reflex record will not be executed on any system.
A common example of this configuration would be to assign the Decision Support System (DSS) as the Delegate System for each production system within an AVEVA Enterprise SCADA environment. This will allow the reflex record to execute on the DSS instead of the system that owns the trigger record.
Notes: If the record assigned as the trigger does not have a dataset, then it will be executed on all systems regardless of the Target System configuration.
The configured limit for the maximum number of reflex records that can be active at any given time is zero by default. this means that the application will not limit the number of active commands. If the value is set to something other than zero, then the application will limit the number of active commands, and any subsequent commands will wait until the count drops below the limit.