Test BLT objects with the Business Object Test Client
- Last UpdatedApr 24, 2025
- 2 minute read
To execute and test a BLT
-
On the desktop, double-click the Windows PowerShell for DNA shortcut.
Windows PowerShell for DNA opens.
-
Execute the following commands:
set-silo Common
blttestclient
The OASyS DNA Business Object Test Client displays.

-
Enter the Host Name, or where the BLT objects reside. In most instances, this is the local computer, or localhost.
-
Select the Component Name dropdown, and choose a BLT, for example SetPointAnalogCommand.
-
Select the Locale to determine which locale will be used for internationalization settings.
-
(Optional) Modify the Timeout (secs), and Max Return Rows to specify the timeout period and number of rows to return after you execute the BLT, respectively.
-
Select your Time Zone.
-
(Optional) If required, enter the changeset number to associate with the BLT in the Changeset field.
-
Select the Input Parameters tab, and based on the BLT object selected, enter the appropriate input parameters to test the BLT object.
For information on the specific input parameters that you must define for a given BLT, refer to the appropriate BLT documentation.
An example set of Input Parameters are shown below.

-
Select the Syntax tab.
The Syntax tab lists the required output parameters that you must define for the BLT selected, if applicable. If output parameters are available for the selected BLT, you must provide them on the Output Parameters tab.
-
Select Execute. If the BLT object test executes successfully, a dialog will display noting the success. Alternatively, if it fails, a dialog will display noting the failure.

-
Select the Results tab to view the BLT object test results.