Configure a Synthetic valve
- Last UpdatedApr 24, 2025
- 3 minute read
The selected valve record will represent a collection of real valves in the field if the Valve Type is configured as a Synthetic Valve.
When the Valve Type is configured as a Synthetic Valve:
-
A Connection Type can be configured.
-
The Path must be specified (underlying multistate or status record).
-
You can configure how each state of the underlying point in interpreted (State Configuration).
-
(Optional) Command Open may be configured if it is supported by the underlying point.
-
(Optional) Command Close may be configured if it is supported by the underlying point.
-
(Optional) Command Stop may be configured if it is supported by the underlying point.
-
You cannot set a Logic Excluded Mode Time Out.
-
Inhibits cannot be configured. Alarm and Event inhibit flags are configured on the underlying point.
To configure a Synthetic valve
-
Open the valve record. For more information on opening a valve record, see Opening the Valve Record.
The valve Row Edit dialog appears.

-
From the Valve Type dropdown list, select either Synthetic PLC-based or Synthetic SCADA host-based.
-
(Optional) In the Priority Display field, enter the priority display for the valve.
Note: If a valve record is automatically created by the Flow Network, the Priority Display configuration of the underlying status/multistate record will be inherited. Administrators and Controllers can later change the Priority Display field on the valve or the underlying record independent of each other.
-
(Optional) In the Parent Valve field, select (...).
The Parent valve dialog appears.

-
Select the Name of the Parent valve record. Select Accept.
-
In the Connection Type field, select Series or Parallel. For more information, see Understand connection types.
-
In the Path field, select (...).
Note: Synthetic Valves require a Path to be selected to provide input and output telemetry for the valve record.
The Path Selector dialog appears.

-
From the Table dropdown list, select status or multistate.
-
In the Record field, select (...).
Depending on the table selection, the status or the multistate dialog will appear. For more information, refer to the Advanced Database Editor (ADE) Administrator documentation.

-
Select the Name of the record. Select Accept.
-
From the Path Selector dialog, select Accept.
-
Configure the State Configuration. For more information, see to State Configuration dialog box.
-
(Optional) Configure the valve command state for the Command Open field. For more information, see Configure the valve command state.
-
(Optional) Configure the valve command state for the Command Close field. For more information, see Configure the valve command state.
-
(Optional) Configure the valve command state for the Command Stop field. For more information, see Configure the valve command state.
-
Save the record.
-
If the selected Parent Valve was not a synthetic or logical valve, you will receive a warning, and the record will not be saved.

Notes: For Synthetic Valves, Inhibits cannot be configured from the Inhibits tab.
Inhibit settings on the point selected in the Path field will be used when generating alarms and events.