AVEVA Pipeline Operations for Liquids

Understand Batch Tracking alarms and events

  • Last UpdatedApr 24, 2025
  • 7 minute read

The following table provides details for configuring the Batch Tracking alarm and event messages.

Note: The messages noted in the table are designated as either alarms that generate identical events or as simple events. In all cases, you can customize the message text and, where applicable, adjust the alarm severity. To update the alarm/event message, refer to the msgInfo table row for the Alarm Message Identifier of interest. For more information on configuration using the msgInfo table, refer to Volume 1 of the RealTime Administrator documentation.

Alarm/Event

Alarm/Event Message Configuration

Alarm Severity Configuration

Type

main_batch_track():Closed loop checking failed in pipeline [pipelineName]. Deactivated. See OASErrLog.

PPL_CLOSED_LOOP_CHECKING_FAILED

Base Message

Alarm and Event

PIPE MODEL ERR: Deactivating pipeline [name]. Contact SCADA Admin. See oasErrLog.

PPL_DEACTIVATING_PIPELINE

Base Message

Alarm and Event

Clearing any PIPE MODEL ERR alarms on pipeline [PipelineName].

PPL_CLRING_ANY_PIPE_MDL_ERR_ALARM_ON_PIPELINE

PPL_CLRING_ANY_PIPE_MDL_ERR_ALARM_ON_PIPELINE

Alarm and Event

Batch [batchId] is off route at pipe [pipe name].

PPL_BATCH_OFF_ROUTE

Base Message

Alarm and Event

Unexpected Flow Difference -IN =[volume in] OUT = [volume out]dband=[flow difference deadband]: @[remote name]: node [node name].

PPL_UNEXPECTED_FLOW_DIFF_IN_OUT_VOL_ALARM

Base Message

Alarm

Unexpected Flow Difference -IN =[volume in] OUT = [volume out]dband=[flow difference deadband].

PPL_UNEXPECTED_FLOW_DIFF_IN_OUT_VOL_EVENT

Base Message

Event

Invalid configured merge pipe [pipe name] at node [node].

PPL_INVALID_CONFIG_MERGE_AT_NODE

Base Message

Alarm and Event

Batch [batchId] merging into Batch [batch ID] at node [node name], Product Type differs.

PPL_BATCH_MERGE_AT_NODE_PROD_TYPE_DIFFERS

Base Message

Alarm and Event

Pressure is above maximum allowable pressure in pipeline [name].

PPL_PRESSURE_ABOVE_HIHI_MAX_ALLOWABLE

PPL_PRESSURE_ABOVE_HIHI_MAX_ALLOWABLE

Alarm and Event

Pressure returned to normal in pipeline [pipelineName].

PPL_PRESSURE_RETURNED_NORMAL

PPL_PRESSURE_RETURNED_NORMAL

Alarm and event

Pressure is [value] from ground elevation in pipeline [name].

PPL_PRESSURE_FROM_LO_GROUND_ELEVATION

PPL_PRESSURE_FROM_LO_GROUND_ELEVATION

Alarm and Event

Pressure is [value] from maximum allowable pressure in pipeline [name].

PPL_PRESSURE_FROM_HI_MAX_ALLOWABLE

PPL_PRESSURE_FROM_HI_MAX_ALLOWABLE

Alarm and Event

Pressure is below ground elevation in pipeline [name].

PPL_PRESSURE_BELOW_LOLO_GROUND_ELEVATION

PPL_PRESSURE_BELOW_LOLO_GROUND_ELEVATION

Alarm and Event

Pipe Segment - [segmentName]: Unable to reconcile telemetered and calculated downstream pressures.

PPL_UNABLE_RECONCILE_DS_PRESSURE_IN_PIPE

Base Message

Alarm

Batch Tracking for [pipelineName] inactive longer than [inactivealarmlimit] minutes:

[pipelineName]: [pipelineDescription].

PPL_BT_PIPELINE_INACTIVE_LONGER_THAN_MINUTES

PPL_BT_PIPELINE_INACTIVE_LONGER_THAN_MINUTES

Alarm and Event

Anomaly Detect triggered: [anomaly detect name]: Detected [number of anomalies].

PPL_ANOMALY_DETECT

PPL_ANOMALY_DETECTED

Base Message

Alarm and Event

Anomaly [anomalyName] has arrived at node [nodeName] in pipeline[pipelineName].

PPL_ANOMALY_ARRIVED_AT_NODE

Base Message

Alarm and Event

Anomaly Detect triggered: [anomaly detect name]: VOL DB-[exceeded deadband] early.

PPL_ANOMALY_DETECT_VOL_DB_EARLY

Base Message

Alarm and Event

Anomaly Detect triggered: [anomaly detect name]: VOL DB-[exceeded deadband] late.

PPL_ANOMALY_DETECT_VOL_DB_LATE

Base Message

Alarm and Event

Anomaly Detect triggered: [anomaly detect name]: TIME DB-[time deadband] early.

PPL_ANOMALY_DETECT_TIME_DB_EARLY

Base Message

Alarm and Event

Anomaly Detect triggered: [anomaly detect name]: MISSED [number of anomalies not found].

PPL_ANOMALY_DETECT_MISSED_ANOMALIES

Base Message

Alarm and Event

Unable to determine downstream segment for anomaly {anomaly original name}. A clone has been created for each downstream segment.

PPL_ANOMALY_CLONE

PPL_ANOMALY_CLONE

Alarm and Event

DETECT [meterPath]: Split a ticket to [detectName] [meterName]: [currentBatch]/[nextBatch].

PPL_DETECT_SPLIT_A_TICKET_TO

Base Message

Alarm and Event

DETECT [meterPath]: Started a ticket at [detectName] [meterName]: [currentBatch]/[nextBatch].

PPL_DETECT_STARTED_A_TICKET_AT

Base Message

Alarm and Event

ADETECT: [anomalyDetectorName] - Alarms reset.

PPL_ANOMALY_DETECT_ALARMS_RESET

Base Message

Alarm and Event

DETECT: [anomalyDetectorName] - Retry search for [currentbatchwhichismissed/nextbatch].

PPL_DETECT_RETRY_SEARCH

Base Message

Alarm and Event

DETECT: [DetectorName] - Alarms reset.

PPL_DETECT_ALARMS_RESET

Base Message

Alarm and Event

Configuration Failure for batch [batch name] in segment [pipe segment name], please see log for details.

PPL_BATCH_CONFIG_FAILURE_IN_PIPE

N/A

Event

Volume Correction Error for Pipeline: [PipelineName] - Please see events and logs for details.

PPL_VOL_CORRECTION_ERR_FOR_PIPELINE

PPL_VOL_CORRECTION_ERR_FOR_PIPELINE

Alarm and Event

Volume Correction Error Returned to Normal for Pipeline: [PipelineName].

PPL_VOL_CORRECTION_ERR_RTN_FOR_PIPELINE

PPL_VOL_CORRECTION_ERR_RTN_FOR_PIPELINE

Alarm and Event

Volume Calculation Error Returned to Normal for Segment [SegmentName].

PPL_VOL_CALCULATION_ERR_RTN_FOR_SEGMENT

N/A

Event

Volume Calculation Failure for Segment [SegmentName] - Please see log for details.

PPL_VOL_CALCULATION_FAIL_FOR_SEGMENT

N/A

Event

An unknown failure occurred when attempting to invoke VolumeCorrectionLibrary for batch [batch name] in pipe_segment [pipeline segment name].

PPL_UNKNOWN_FAILURE_BATCH_INVOKE_VOL_CORRECTION_LIB

N/A

Event

Changed davg from [Old Value] to [New Value] in batch id [BatchID Name].

PPL_AVG_DENSITY_CHANGED_IN_BATCH

N/A

Event

Product Type: [ProductTypeSlotNumber] not found within [dband][unit] upstream of [tableName].[meterName].

PPL_PRODUCT_TYPE_NOT_FOUND_UPSTREAM

PPL_PRODUCT_TYPE_NOT_FOUND_UPSTREAM

Alarm

Product Type: [ProductTypeSlotNumber] not found within [dband][unit] downstream of [tableName].[meterName].

PPL_PRODUCT_TYPE_NOT_FOUND_DOWNSTREAM

PPL_PRODUCT_TYPE_NOT_FOUND_DOWNSTREAM

Alarm

Failed to load replicated pipeline [pipeline name].

PPL_FAILED_TO_LOAD_REPLICATED

PPL_FAILED_TO_LOAD_REPLICATED

Alarm and Event

REVERT failed – [error message] - on file [filename].

PPL_REVERT_FAILED_ON_FILE_FILENAME

PPL_REVERT_FAILED_ON_FILE_FILENAME

Alarm and Event

Pipeline reverted using file [Filepath and Filename].

PPL_REVERTED_USING_FILE

Base Message

Alarm and Event

Unable to read pipeline name.

PPL_REVERT_FAILED_UNABLE_TO_READ_PIPELINE_NAME

PPL_REVERT_FAILED_UNABLE_TO_READ_PIPELINE_NAME

Alarm and Event

Unable to delete pipeline associated child records.

PPL_REVERT_FAILED_UNABLE_TO_DEL_PPL_CHLD_REC

PPL_REVERT_FAILED_UNABLE_TO_DEL_PPL_CHLD_REC

Alarm and Event

Could not determine group on Pipeline [pipelineName].

PPL_REVERT_FAILED_COULD_NOT_DETERMINE_GROUP

PPL_REVERT_FAILED_COULD_NOT_DETERMINE_GROUP

Alarm and Event

Cannot lock pipeline [pipelineRecordNumber.

PPL_REVERT_FAILED_CANNOT_LOCK_PIPELINE

PPL_REVERT_FAILED_CANNOT_LOCK_PIPELINE

Alarm and Event

Pipeline [pipelineName]still active.

PPL_REVERT_FAILED_PIPELINE_STILL_ACTIVE

PPL_REVERT_FAILED_PIPELINE_STILL_ACTIVE

Alarm and Event

Pipeline [pipelineName] not found in database.

PPL_REVERT_FAILED_PIPELINE_NOT_FOUND_IN_DB

PPL_REVERT_FAILED_PIPELINE_NOT_FOUND_IN_DB

Alarm and Event

Use BTC -r [pipelineName] to reload.

PPL_REVERT_FAILED_USE_BTC_TO_RELOAD

PPL_REVERT_FAILED_USE_BTC_TO_RELOAD

Alarm and Event

Database locking problems. See batErrLog.

PPL_REVERT_FAILED_DATABASE_LOCKING_PROBLEMS

PPL_REVERT_FAILED_DATABASE_LOCKING_PROBLEMS

Alarm and Event

Unable to read file.

PPL_REVERT_FAILED_UNABLE_TO_READ_FILE

PPL_REVERT_FAILED_UNABLE_TO_READ_FILE

Alarm and Event

Corrupt pipeline record.

PPL_REVERT_FAILED_CORRUPT_PIPELINE_RECORD

PPL_REVERT_FAILED_CORRUPT_PIPELINE_RECORD

Alarm and Event

Corrupt record. See batErrLog.

PPL_REVERT_FAILED_CORRUPT_RECORD

PPL_REVERT_FAILED_CORRUPT_RECORD

Alarm and Event

Node [nodeName] has corrupt pipeline reference.

PPL_REVERT_FAILED_NODE_HAS_CORRUPT_PPL_REF

PPL_REVERT_FAILED_NODE_HAS_CORRUPT_PPL_REF

Alarm and Event

Detect [detectName] has corrupt pipeline reference.

PPL_REVERT_FAILED_DETECT_HAS_CORRUPT_PPL_REF

PPL_REVERT_FAILED_DETECT_HAS_CORRUPT_PPL_REF

Alarm and Event

Adetect

[anomalyDetectName] has corrupt pipeline reference.

PPL_REVERT_FAILED_ADETECT_HAS_CORRUPT_PPL_REF

PPL_REVERT_FAILED_ADETECT_HAS_CORRUPT_PPL_REF

Alarm and Event

Section [sectionName] has corrupt pipeline reference.

PPL_REVERT_FAILED_SECTION_HAS_CORRUPT_PPL_REF

PPL_REVERT_FAILED_SECTION_HAS_CORRUPT_PPL_REF

Alarm and Event

Pipe [pipelineName] has corrupt pipeline reference.

PPL_REVERT_FAILED_PIPE_HAS_CORRUPT_PPL_REF

PPL_REVERT_FAILED_PIPE_HAS_CORRUPT_PPL_REF

Alarm and Event

Connectivity [recordNumber] has corrupt pipeline reference.

PPL_REVERT_FAILED_CONNECTIVITY_HAS_CRPT_PPL_REF

PPL_REVERT_FAILED_CONNECTIVITY_HAS_CRPT_PPL_REF

Alarm and Event

Database is full. See batErrLog.

PPL_REVERT_FAILED_DATABASE_IS_FULL

PPL_REVERT_FAILED_DATABASE_IS_FULL

Alarm and Event

Revert file not current.

PPL_REVERT_FAILED_REVERT_FILE_NOT_CURRENT

PPL_REVERT_FAILED_REVERT_FILE_NOT_CURRENT

Alarm and Event

Record creation problems. See batErrLog.

PPL_REVERT_FAILED_RECORD_CREATION_PROBLEMS

PPL_REVERT_FAILED_RECORD_CREATION_PROBLEMS

Alarm and Event

Anomaly [anomalyName] arriving in [no of minutes] minute/s in pipeline [pipelineName].

PPL_ANOMALY_ARRIVING_IN_MINUTES

Base Message

Alarm and Event

Anomaly [anomalyName] is [volume] [Volume Unit] [upstream| downstream] from [nodeDisplayName] in pipeline [pipelineName].

PPL_ANOMALY_IS_VOL_FROM_NODE

Base Message

Alarm and Event

Deleting Fragment [Fragment name] from batch ID [Batch name].

PPL_DELETING_FRAGMENT_FROM_BATCH

N/A

Event

Fragment [Fragment name] changed from batch [Batchname] to batch [BatchName].

PPL_FRAGMENT_CHANGED_FROM_BATCH

N/A

Event

Attempt to save backup file for pipeline [Pipeline name] failed.

PPL_ATTEMPT_SAVE_BKP_FILE_FOR_PIPELINE_FAILED

Base Message

Alarm and Event

[interface] FOUND On time.

PPL_INTERFACE_DT_FOUND_ON_TIME

Base Message

Alarm and Event

<interface> too close.

PPL_INTERFACE_DETECT_TRIGGERED_TOO_CLOSE

Base Message

Alarm and Event

<interface> Early-<volume offset from detector location>bbl.

PPL_INTERFACE_DETECT_TRIGGERED_EARLY

Base Message

Alarm and Event

<interface> Late-<volume offset from detector location>bbl.

PPL_INTERFACE_DETECT_TRIGGERED_LATE

Base Message

Alarm and Event

Gave up on interface detection for <interface>.

PPL_INTERFACE_GAVE_UP_ON_INTERFACE_DETECTION

Base Message

Alarm and Event

Threshold calc OK.

PPL_INTERFACE_THRESHOLD_CALCULATION_OK

Base Message

Alarm and Event

Interface Detect triggered: [detectName]:[alarmState]: Threshold calc OK :[currentBatch]/[nextBatch] Not found in [abs_vol] [Volume Unit].

PPL_INTERFACE_THRESHOLD_CALCULATION_OK

Base Message

Alarm and Event

Interface Detect triggered:[detectName]:[alarmState]:[currentBatch]/[nextBatch] MISSED beyond downstream node.

PPL_INTERFACE_DT_BATCH_MISSED_BEYOND_DS_NODE

Base Message

Alarm and Event

Interface Detect triggered:[detectName]:[alarmState]:[currentBatch]/[nextBatch] FOUND beyond downstream node.

PPL_INTERFACE_DT_BATCH_FOUND_BEYOND_DS_NODE

Base Message

Alarm and Event

Interface Detect triggered:[detectName]:[alarmState]:[currentBatch]/[nextBatch] FOUND before upstream node.

PPL_INTERFACE_DT_BATCH_FOUND_BEFORE_US_NODE

Base Message

Alarm and Event

Batch [batchid] arriving at [nodeDisplayName] in [no of minutes] minute/s in pipeline [pipelineName].

PPL_BATCH_ARRIVING_AT_NODE_IN_MINUTES

Base Message

Alarm and Event

Anomaly [anomalyName] arriving at [nodeDisplayName] in [no of minutes] minute/s in pipeline [pipelineName].

PPL_ANOMALY_ARRIVING_AT_NODE_IN_MINUTES

Base Message

Alarm and Event

Batch [batchid] arriving in [no of minutes] minute/s in pipeline [pipelineName].

PPL_BATCH_ARRIVING_IN_MINUTES

Base message

Alarm and Event

Batch [batchId] is [volume] [Volume Unit] from [nodeDisplayName] in pipeline [pipelineName].

PPL_BATCH_IS_VOL_FROM_NODE

Base Message

Alarm and Event

Batch [batchid] has arrived at [nodename] in pipeline [pipelineName].

PPL_BATCH_ARRIVED_AT_NODE

Base Message

Alarm and Event

Pipeline [pipeline name] has an invalid Unit Profile configuration in [pipe segment count] pipe segment(s). Pipeline deactivated. See oasErrLog for detail.

PPL_INVALID_UNIT_PROF_CONFIG_DEACTIVATED

Base Message

Alarm and Event

Pipeline [pipeline name] has an invalid Unit Profile configuration in [piepsegment count] pipe segment(s). Attempt to deactivate pipeline failed. See oasErrLog for detail.

PPL_INVALID_UNIT_PROF_CONFIG_DEACTIVATE_FAIL

Base Message

Alarm and Event

Pipeline [pipelineName] Segment [segmentName] has invalid or unsupported type on Flow Rate Source Path.

PPL_SEGMENT_INVALID_FLOWRATESOURCEPATH

PPL_SEGMENT_INVALID_FLOWRATESOURCEPATH

Alarm and Event

Pipeline [pipelineName] Segment [segmentName] Flow Rate Source path configuration error has been resolved.

PPL_SEGMENT_INVALID_FLOWRATESOURCEPATH_RTN

PPL_SEGMENT_INVALID_FLOWRATESOURCEPATH_RTN

Alarm and Event

Pipeline [pipelineName] Linepack Calculation Method configuration error has been resolved.

PPL_INVALID_LINEPACK_CALC_METHOD_RTN

PPL_INVALID_LINEPACK_CALC_METHOD_RTN

Alarm and Event

Configuration error. Pipeline [pipelineName] has invalid enumeration value of [enumValue]on Linepack Calculation Method. Contact your system administrator.

PPL_INVALID_LINEPACK_CALC_METHOD

PPL_INVALID_LINEPACK_CALC_METHOD

Alarm and Event

Configuration error. Pipeline [pipelineName] Segment [segmentName] has invalid auto inhibit path on pressure downstream transmitter input. Contact your system administrator.

PPL_SEGMENT_INVALID_PRESS_DNS_TRANS

PPL_SEGMENT_INVALID_PRESS_DNS_TRANS

Alarm and Event

Pipeline [pipelineName] Segment [segmentName] pressure downstream transmitter input configuration error has been resolved.

PPL_SEGMENT_INVALID_PRESS_DNS_TRANS_RTN

PPL_SEGMENT_INVALID_PRESS_DNS_TRANS_RTN

Alarm and Event

Configuration error. Pipeline [pipelineName] Segment [segmentName] has invalid auto inhibit path on pressure upstream transmitter input. Contact your system administrator.

PPL_SEGMENT_INVALID_PRESS_UPS_TRANS

PPL_SEGMENT_INVALID_PRESS_UPS_TRANS

Alarm and Event

Pipeline [pipelineName] Segment [segmentName] pressure upstream transmitter input configuration error has been resolved.

PPL_SEGMENT_INVALID_PRESS_UPS_TRANS_RTN

PPL_SEGMENT_INVALID_PRESS_UPS_TRANS_RTN

Alarm and Event

Configuration error. Pipeline [pipelineName] Segment [segmentName] has invalid auto inhibit path on temperature downstream transmitter input. Contact your system administrator.

PPL_SEGMENT_INVALID_TEMP_DNS_TRANS

PPL_SEGMENT_INVALID_TEMP_DNS_TRANS

Alarm and Event

Pipeline [pipelineName] Segment [segmentName] temperature downstream transmitter input configuration error has been resolved.

PPL_SEGMENT_INVALID_TEMP_DNS_TRANS_RTN

PPL_SEGMENT_INVALID_TEMP_DNS_TRANS_RTN

Alarm and Event

Configuration error. Pipeline [pipelineName] Segment [segmentName] has invalid auto inhibit path on temperature upstream transmitter input. Contact your system administrator.

PPL_SEGMENT_INVALID_TEMP_UPS_TRANS

PPL_SEGMENT_INVALID_TEMP_UPS_TRANS

Alarm and Event

Pipeline [pipelineName] Segment [segmentName] temperature upstream transmitter input configuration error has been resolved.

PPL_SEGMENT_INVALID_TEMP_UPS_TRANS_RTN

PPL_SEGMENT_INVALID_TEMP_UPS_TRANS_RTN

Alarm and Event

Anomaly Detect launched: [anomaly Name].

PPL_ANOMALY_DETECT_LAUNCHED

PPL_ANOMALY_DETECT_LAUNCHED

Alarm and Event

Anomaly Detect received: [anomaly Name].

PPL_ANOMALY_DETECT_RECEIVED

PPL_ANOMALY_DETECT_RECEIVED

Alarm and Event

Anomaly Detect error occurred - please see log for details.

PPL_ANOMALY_DETECT_ERROR

PPL_ANOMALY_DETECT_ERROR

Alarm and Event

Anomaly Detect triggered: [anomaly Name] (UPS-NORMAL [anomaly location] {2})

PPL_ANOMALY_DETECT_UPS_NORMAL

PPL_ANOMALY_DETECT_UPS_NORMAL

Alarm and

Event

Anomaly Detect triggered: [anomaly Name] (DNS-NORMAL [anomaly location] {2})

PPL_ANOMALY_DETECT_DNS_NORMAL

PPL_ANOMALY_DETECT_DNS_NORMAL

Alarm and

Event

Anomaly Detect triggered: [anomaly Name] (UPS-EARLY [anomaly location] {2})

PPL_ANOMALY_DETECT_UPS_EARLY

PPL_ANOMALY_DETECT_UPS_EARLY

Alarm and

Event

Anomaly Detect triggered: [anomaly Name] (DNS-LATE [anomaly location] [volume unit])

PPL_ANOMALY_DETECT_DNS_LATE

PPL_ANOMALY_DETECT_DNS_LATE

Alarm and

Event

Anomaly Detect triggered: [anomaly Name] (UPS-TOO-EARLY [anomaly location] [volume unit])

PPL_ANOMALY_DETECT_UPS_TOO_EARLY

PPL_ANOMALY_DETECT_UPS_TOO_EARLY

Alarm and

Event

Anomaly Detect triggered: [anomaly Name] (DNS-TOO-LATE [anomaly location] [volume unit])

PPL_ANOMALY_DETECT_DNS_TOO_LATE

PPL_ANOMALY_DETECT_DNS_TOO_LATE

Alarm and

Event

Anomaly Detect triggered: MISSING-ETA [anomaly Name]

PPL_ANOMALY_DETECT_MISSING_ETA

PPL_ANOMALY_DETECT_MISSING_ETA

Alarm and

Event

Anomaly Detect missing: [anomaly Name] (MISSING-SIGNAL [anomaly location] [volume unit])

PPL_ANOMALY_DETECT_MISSING_SIGNAL

PPL_ANOMALY_DETECT_MISSING_SIGNAL

Alarm and

Event

Anomaly [anomaly Name] is [volume quantity] [volume unit] away from downstream segment [segment name] which leads to segment(s) that do not expect anomalies of type [anomaly type]: [list of segment names].

PPL_ANOMALY_APPROACHES_UNEXPECTED_SEGMENT

PPL_ANOMALY_APPROACHES_UNEXPECTED_SEGMENT

Alarm and

Event

Anomaly [anomaly Name] has entered segment [segment name] which is or leads to segment(s) that do not expect anomalies of type [anomaly type]: [list of segment names].

PPL_ANOMALY_ENTERED_UNEXPECTED_SEGMENT

PPL_ANOMALY_ENTERED_UNEXPECTED_SEGMENT

Alarm and

Event

Anomaly [anomaly Name] is [volume quantity] [volume unit] away from downstream segment [segment name] which does not lead to the designated receiver: [adetect name] on node [node name].

PPL_ANOMALY_APPROACHES_NO_RECEIVER

PPL_ANOMALY_APPROACHES_NO_RECEIVER

Alarm and Event

Anomaly [anomaly Name] has entered segment [segment name] which does not lead to the designated receiver: [adetect name] on node [node name].

PPL_ANOMALY_ENTERED_NO_RECEIVER

PPL_ANOMALY_ENTERED_NO_RECEIVER

Alarm and Event

Slip factor for anomaly [anomaly name] changed from [previous slip factor] to [current slip factor], because anomaly moved from [previous segment] to [current segment].

PPL_ANOMALY_SLIP_FACTOR_CHANGED

PPL_ANOMALY_SLIP_FACTOR_CHANGED

Event