Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA Enterprise SCADA

String keys used by the Re-Alarming feature

  • Last UpdatedApr 24, 2025
  • 1 minute read

The following configuration settings are located in the %DNADataRoot%\RealTime\sdk\resx\libappResources\realarmStrings.resx file:

<data name="RE_ALARM_SUFFIX">

<value xml:space="preserve"> -reAlarm</value>

<comment xml:space="preserve">code=-1001</comment>

</data>

<data name="RE_ALARM_PREFIX">

<value xml:space="preserve">ReAlarm- </value>

<comment xml:space="preserve">code=-1002</comment>

</data>

<data name="RE_ALARM_LEVEL_REGEX">

<value xml:space="preserve">.* Level = [0-9]+.*</value>

<comment xml:space="preserve">code=-1003</comment>

</data>

<data name="RE_ALARM_VALUE_REGEX">

<value xml:space="preserve">.* Value = [0-9]+.*</value>

<comment xml:space="preserve">code=-1004</comment>

</data>

<data name="RE_ALARM_INSTR_FAIL_REGEX">

<value xml:space="preserve">INSTR FAIL(.*)</value>

<comment xml:space="preserve">code=-1005</comment>

</data>

The = character cannot be replaced in the previous configuration settings because it is used internally to locate the value in alarms for analog, rate, and flowtotalconfig records.

If the word Value in the RE_ALARM_VALUE_REGEX configuration setting must be translated, it is important to notice that it is a regular expression. The following configuration settings must also be translated to satisfy the regular expression:

  • %DNADataRoot%\RealTime\sdk\resx\libappResources\realarmStrings.resx:

    • RE_ALARM_VALUE_REGEX

  • %DNADataRoot%\RealTime\sdk\resx\libappResources\krunchStrings.resx:

    • KRN_VALUE

    • KRN_ROCVALUE

    • KRN_ROCVALUE_BASELINE

    • KRN_VALUE_INST_FAIL_SCALED

    • KRN_INST_FAIL_RAW

    • KRN_VALUE_ABS

    • KRN_FLATLINE_ALM