Easy eXtended Operator Station (ezXOS) alarm attribute (xosalmattr) records are used to assign colors and sound to different alarm severities. The xosalmattr table contains the following internal fields:

Internal Field Name

Data Type

Description

accessFlag

displayname

This flag is used by easy eXtended Operator Station (ezXOS) to determine whether a table is being modified through the Advanced Database Editor (ADE). If the flag is set, access to the table is denied.

audiofile

filename

This field is the wave file that is used for annunciation for the particular alarm severity. For the sound to be properly played in the ezXOS station, the wave file should exist in the %DNADataRoot%\Shared\elements\sounds directory. This directory is in the following (typical) location: \AVEVA\DNA\Shared\elements\sounds.

delay

unsigned int

Beep cycle time in seconds.

frequency

unsigned int

Number of beeps per cycle.

name

pntname

This field is the unique name of this xosalmattr record. The name can be up to 32 characters in length.

ptnum

unsigned char

This field represents the record’s slot number in the database.

repeat

int

Number of times to repeat the beep cycle.

sevcolor

pntcolor

Color of alarms of this severity.

severity

sev_enum

The severity of the alarm.