Virtualflowcomputer table details
- Last UpdatedApr 24, 2025
- 3 minute read
The virtualflowcomputer table is used by the Virtual Flow Computer (VFC) application. The virtualflowcomputer table is used to contain configuration data and totalized runtime data for a set of meters operating in parallel. The virtualflowcomputer table contains the following internal fields:
|
Internal Field Name |
Data Type |
Description |
|---|---|---|
|
accessFlag |
displayname |
Display that accesses this record. |
|
autoInh |
oas_boolean_t |
Is the VFC inhibited due to an auto-inhibit operation? |
|
autoInhPath |
path |
The path to the status or multistate point to auto-inhibit. |
|
batchGuid |
GUIDstring |
When the Batch ID is changed for a given Virtual Flow Computer in ADE, a GUID is automatically generated. This field is not visible in ADE. |
|
batchId |
batchname |
Optional value to use for Batch ID in batch tracking. |
|
csw |
double |
Correction for sediment or water (0-100%). |
|
DailyIntegrated |
PeriodicIntegration |
Daily integrated data. |
|
dataset |
doas_dset_slot |
This field indicates the dataset to which the record is assigned. Datasets are used to associate the record with the privileges assigned for each system mode. Once a record is assigned to a dataset value, the dataset can only be changed to a value for which the system has a privilege record. |
|
description |
description |
A description of this VFC point, up to 47 characters in length. |
|
dsysControl |
oas_boolean_t |
Indicate whether the point is controllable from the local system. |
|
enastates |
string80 |
States that enable a meter device. |
|
flag |
flags |
For information on the flag structure, see Flag structure details. |
|
flowrate |
double |
Gross Standard Volume (GSV) flow rate. |
|
flowrateUnitShort |
string16 |
Short form units for flow rate for the record. |
|
gsv |
double |
GSV. |
|
gv |
double |
Gross Volume. |
|
hourlygsv |
double |
Hourly GSV. |
|
hourlygv |
double |
Hourly GV. |
|
HourlyIntegrated |
PeriodicIntegration |
Hourly integrated data. |
|
hourlyiv |
double |
Hourly indicated volume. |
|
hourlynsv |
double |
Hourly Net Standard Volume (NSV). |
|
inhibit |
oas_boolean_t |
Manual inhibit flag. |
|
inhstates |
string80 |
States that inhibit a meter device. |
|
input |
AssignmentInputStruct |
The VFC point assignment configuration details. |
|
iv |
double |
IV. |
|
LastIntegrationRollup |
internaltime |
Datetime of last integrated data rollup. |
|
lasttime |
internaltime |
Last processing time. |
|
lasttopofhour |
internaltime |
The last top of hour processed time. |
|
Mass |
double |
Mass in pounds. |
|
meterFactorAlarm.alminh |
oas_boolean_t |
Inhibit alarms associated with a Meter Factor (mtrfact) record? |
|
meterFactorAlarm.evtinh |
oas_boolean_t |
Inhibit events associated with a mtrfact record? |
|
meterFactorAlarm.sev |
sev_enum |
Alarm severity. |
|
MonthlyIntegrated |
PeriodicIntegration |
Monthly integrated data. |
|
name |
pntname |
The unique name of this virtualflowcomputer record. The name can be up to 32 characters in length. |
|
nsv |
double |
NSV. |
|
PeriodicIntegrationEnabled |
oas_boolean_t |
Indicates periodic integration is enabled. |
|
pipelineslt |
pipelineslot |
The batch track region associated with this virtualflowcomputer record. |
|
pointClass |
configenumslot |
The point class category contains multiple configuration enumerations used for categorical configuration of points. |
|
pointSubClass |
configenumslot |
The point subclass category is a configurable enumeration category used for categorical configurations. It cannot be used for configurable alarms and events. |
|
ppltask |
enum_ppltask |
The type of association for the virtualflowcomputer record to the Batch Tracking pipeline. |
|
presimiv |
double |
Pre-simulation Indicated Volume (IV). |
|
presimgsv |
double |
Pre-simulation gross standard volume. |
|
presimgv |
double |
Pre-simulation gross volume. |
|
prodtype |
prodtypeslot |
The prodtype record that represents the product that flows through the meter. |
|
ptnum |
slot |
Slot number in the RealTime database. |
|
rtu |
remoteslot |
The name of the remote record corresponding to the Remote Terminal Unit (RTU) associated with this virtualflowcomputer record. |
|
simulation |
vfcsimfield |
Simulation fields. |
|
smoothedflowrate |
double |
Smoothed GSV flow rate. |
|
TopOfDay |
internaltime |
Time of day (HH) for the Top of Day (TOD) to occur. |
|
topOfDayAlarmActive |
oas_boolean_t |
Indicates that there is an active Top of Day configuration error alarm on the Virtual Flow Computer record. |
|
TotalIntegrated |
PeriodicIntegration |
Total integrated data. |
|
unitprofile |
unitprofileslot |
The name of the unitprofile record used to assign the units of measurement. |
|
useAutoInh |
oas_boolean_t |
Use a state point to determine inhibit. |
|
UsesGroupTopOfDay |
oas_boolean_t |
Indicates that TopOfDay is overidden by groupTOD.TopOfDay. |
|
vfcassigntype |
enum_pipelineassigntype |
Pipeline task assignment type configuration details. |
|
vfcTime |
internaltime |
Time from rate. Use for PLM stale time check. |
|
wa_press |
double |
Weighted Average Pressure (WAP). |
|
wa_temp |
double |
Weighted Average Temperature (WAT). |
|
wa_dens |
double |
Weighted Average Density (WAD). |
|
wa_obs_dens |
double |
Weighted Average Observed Density (WAOD). |
|
wa_cws |
double |
Weighted average Correction for Sediment and Water (CSW) (0-100%). |
|
wa_flowrate |
double |
Weighted average GSV flow rate. |
|
wa_ctl |
double |
Weighted Average Temperature Correction Factor (WACTL). |
|
wa_cpl |
double |
Weighted Average Pressure Correction Factor (WACPL). |
|
YearlyIntegrated |
PeriodicIntegration |
Yearly integrated data. |