Rtstring function puts

  • Last UpdatedApr 24, 2025
  • 1 minute read

The rtstring table provides two function puts that allow for writing a string value to remotes that support string registers. The syntax is as follows:

Fnput rtstring.<rtstring name> "setval <string value> [CONFIRMED] [CMDAUTO]"

Fnput rtstring.<rtstring name> "setstring <string value> [CONFIRMED] [CMDAUTO]"

Note the following:

  • Since the value string can include CMDAUTO as its substring, this may result in incorrect parsing of the function put command. To avoid this situation, the following rules exist:

    • When CMDAUTO is all uppercase, the system interprets it as a keyword.

    • When CMDAUTO is either lower case or mixed case, the system interprets it as part of the value string.

      Note: This behavior is not consistent with analog, status, and multistate commands.

Examples

  • Fnput rtstring.test "setval valve cmdauto" - the string sent will be "valve cmdauto".

  • Fnput rtstring.test "setval valve CMDAUTO" - the string sent will be "valve" and the function put will be interpreted as an automatic command.