Aceconfig table details
- Last UpdatedApr 24, 2025
- 1 minute read
For information on the aceconfig table, refer to volume 2 of the AVEVA Enterprise SCADA RealTime Administrator documentation. The aceconfig table contains the following internal fields:
|
Internal Field Name |
Data Type |
Description |
|---|---|---|
|
alarmTriggered |
oas_boolean_t |
Trigger the record when records configured as inputs change their alarm state? |
|
codeTriggered |
oas_boolean_t |
Trigger the acecode when there is a change to the acecode? |
|
description |
description |
A description of the point, up to 47 characters in length. |
|
doRun |
oas_boolean_t |
Should the routine run now? |
|
inputTriggered |
oas_boolean_t |
Trigger the record when changes to the inputs, configuration, or code occur? |
|
name |
pntname |
This field displays the name of the aceconfig record. |
|
parameters[0-19].isConstant |
oas_boolean_t |
Use a constant value? Note: parameters[0] is reserved for configuration of the optional output point, leaving 18 possible inputs. |
|
parameters[0-19].dataSource |
AceDataSource_enum |
If isConstant is FALSE, select either Path or PubSub. Note: parameters[0] is reserved for configuration of the optional output point, leaving 18 possible inputs. |
|
parameters[0-19].value |
longstring |
If isConstant is TRUE, this number is the constant input value. If the dataSource is PubSub, this value is the PubSub topic string. Note: parameters[0] is reserved for configuration of the optional output point, leaving 18 possible inputs. |
|
parameters[0-19].paramPath |
path |
The RealTime path to the value. Note: parameters[0] is reserved for configuration of the optional output point, leaving 18 possible inputs. |
|
startupTriggered |
oas_boolean_t |
Trigger the acecode when the system goes Hot? |
|
triggerInterval |
int |
The number of seconds desired between the ACE code (acecode) executions. |
|
updateFresh |
oas_boolean_t |
Does the output fresh flag get set? |