Perform a Rebase (ReSync) on the source (production) zone
- Last UpdatedApr 24, 2025
- 1 minute read
To synchronize the RealTime database (RTDB), you will need to perform a Rebase (ReSync) procedure on the RealTime server in the system that currently owns the production dataset.
To perform a Rebase (ReSync) on the Source (Production) zone
-
Delete all template (*.t) files found in %DNADataRoot%\realtime\database\INTEL_NT.
-
On the desktop, double-click the Windows PowerShell for DNA shortcut.
Windows PowerShell for DNA opens.
Note: If you are accessing Windows PowerShell on a Core computer, switch to Windows PowerShell mode, and load the set-silo cmdlet by executing the following command:
cd %DNAInstallRoot%\Shared\scripts
. .\set-silo.ps1 -
Execute the following commands:
set-silo RealTime
text_save
-
Save a copy of all .l files found in %DNADataRoot%\realtime\database\INTEL_NT to a portable drive, with the exception of the following files:
-
almsum.l
-
area.l
-
CMX_async_trans.l
-
CMX_sync_trans.l
-
doas_dataset.l
-
doas_mode.l
-
doas_mode_group.l
-
doas_privilege.l
-
doas_slotrange.l
-
group.l
-
groupAreaJoin.l
-
XIS_async_trans.l
-
XIS_sync_trans.l
-
xoslogins.l
-
-
Create a backup of the Application Calculation Engine (ACE) source files to a portable drive.