Adetect table details
- Last UpdatedApr 24, 2025
- 2 minute read
Certain devices (represented by a status or multistate record) are used to detect a pig or other type of anomaly that may exist on the pipeline. The Batch Tracking application uses records in the adetect table to link these devices to the pipeline locations. The adetect table contains the following internal fields:
|
Internal Field Name |
Data Type |
Description |
|---|---|---|
|
adetectType |
adetectTypeEnum |
The nature of the anomaly detector type. |
|
anmtype |
anmtypeslot |
The nature of the anomaly type. |
|
dataset |
doas_dset_slot |
This field indicates the dataset to which the record is assigned. Datasets are used to associate the record with the privileges assigned for each system mode. Once a record is assigned to a dataset value, the dataset can only be changed to a value for which the system has a privilege record. |
|
deadband_minus |
double |
The volume zone downstream of the detector location. |
|
deadband_plus |
double |
The volume zone upstream of the detector location. |
|
description |
description |
A description of what this action sequence does, up to 47 characters in length. |
|
downstreamNormalDetectionVolume |
double |
The downstream normal detection window. |
|
downstreamLateDetectionVolume |
double |
The downstream late detection volume. |
|
flag.alminh |
oas_boolean_t |
Prevent alarms from being generated when a sequence fails to complete successfully? |
|
flag.bmsg |
messageslot |
The message associated with the record. |
|
flag.evtinh |
oas_boolean_t |
Prevent events from being generated when a sequence fails to complete successfully? |
|
flag.severity |
unsigned char |
The severity level of the alarm. |
|
group |
groupslot |
This field shows the group that this point is associated with for alarming. |
|
inh |
oas_boolean_t |
Inhibit the record? |
|
inhAnomalyLaunchedAlarm |
oas_boolean_t |
Inhibit alarms for when an anomaly is launched? |
|
inhAnomalyReceivedAlarm |
oas_boolean_t |
Inhibit alarms for when an anomaly is received? |
|
inhDetectionEarlyOrLateAlarm |
oas_boolean_t |
Inhibit alarms for early or late detection. |
|
inhDetectionNormalAlarm |
oas_boolean_t |
Inhibit alarms for normal detection. |
|
inhDetectionTooEarlyOrLateAlarm |
oas_boolean_t |
Inhibit alarms for too early or too late detection. |
|
inhMissEtaOnSignalAlarm |
oas_boolean_t |
Inhibit an alarm when a detection occurs but there is no Estimated Time of Arrival (ETA) record for this anomaly. |
|
inhMissSignalOnEtaTooLateAlarm |
oas_boolean_t |
Inhibit an alarm when an anomaly leaves the late detection window without a signal. |
|
lasttimeStateTriggered |
internaltime |
This field indicates the last timestamp for when the trigger point transitions to triggered state. When the trigger point transitions out of triggered state, the value is set to zero. |
|
name |
pntname |
The name of the adetect record. |
|
node |
nodeslot |
The related node. |
|
pipeline |
pipelineslot |
The associated pipeline. |
|
receiverAdetectSlot |
adetectslot |
The Receiver adetect associated with this adetect record—only applicable if this adetect is of type Launcher. |
|
t_deadband |
long |
The early time limit. |
|
triggerPointPath |
path |
The path to the status, multistate, or ALPConfig record to be used as the trigger for the anomaly detection. |
|
triggerState |
msgstring |
The message set state of the status, multistate, or ALPConfig result required to signal the anomaly detection. |
|
triggerStateNumber |
int |
The ptnum of the message set state of the status or multistate, or the result of the ALPConfig. |
|
upstreamEarlyDetectionVolume |
double |
Upstream Early Detection Volume. |
|
upstreamNormalDetectionVolume |
double |
Upstream Normal Detection Volume. |