Configure the minimum integrity update poll time
- Last UpdatedApr 24, 2025
- 1 minute read
An automated integrity update poll will be executed against the remote record when a triggered condition clears on the associated Flatline Watchdog (watchdog) record that has the Integrity Update field enabled. The integrity update poll processes the current data and updates the data quality for all telemetered points associated with the remote record. To avoid several automated integrity update polls against remote records from occurring too quickly, a delay time needs to be configured on the remote record.
To configure the minimum integrity update poll delay time for a remote record
-
Navigate to the Main tab in the remote Row Edit dialog box.

-
In the Minimum Integrity Poll Delay (sec) field, enter the minimum time between integrity update polls for this remote record. A zero (0) is not accepted as a valid minimum time value and will default to a value of 10 seconds. All other positive values are permitted.
Notes: The Minimum Integrity Poll Delay (sec) field is only used for automated integrity update polls when a watchdog record is configured to perform an integrity update (that is, the Integrity Update checkbox is selected). It does not limit on-demand integrity update poll requests.
Not all protocol drivers support integrity update poll requests.