Doas_privilege table details
- Last UpdatedApr 24, 2025
- 2 minute read
For distributed systems, doas_privilege is used to establish the operating permissions that are related to a doas_dataset for a system under an active doas_mode.
Fields in the RealTime doas_privilege table
|
ADE Field Name |
Internal Field Name |
Data Type |
Descriptions |
|---|---|---|---|
|
n/a |
accessFlag |
pntname |
This flag is used by ezXOS to determine whether or not a table can be modified through the ADE. If the flag is set, access to the table is denied. |
|
Enable Statistics |
accumulate |
oas_boolean_t |
This field indicates whether or not the records that are using this dataset should enable statistical processing. |
|
Alarm |
alarm |
doasAlarmType |
This field indicates whether or not the records that are using the dataset should ignore alarms, silently update alarm summaries, or enable full alarm support.
|
|
Collect Override |
collect |
oas_boolean_t |
This flag is used by Collect software to determine whether or not the collect data belonging to the related dataset is gathered and stored locally. This should be set to OFF where Historical data replication (via either Datapump or MS Replication software) is configured for the system. Refer to the Historical Administrator documentation. Note: This field is deprecated and will be removed in a future release. |
|
Configure |
configure |
oas_boolean_t |
This field indicates whether or not the records that are using this dataset can be configured. |
|
Control |
control |
oas_boolean_t |
This field indicates whether or not the records that are using this dataset can be configured. |
|
Dataset |
dataset |
doas_dset_slot |
This field shows the associated dataset, and is used to associate the privileges that are assigned for each system in each operating mode within distributed systems. |
|
Event |
event |
oas_boolean_t |
This field indicates whether or not event logs are recorded for the records that are using this dataset. |
|
Mode |
mode |
doas_mode_slot |
The associated doas_mode. |
|
Name |
name |
doas_priv_na me |
The privilege’s name. |
|
Ownership |
owns |
oas_boolean_t |
This field indicates whether or not the records that are using this dataset are owned by the system. Data acquisition and calculations are performed only when ownership privilege has been granted. |
|
n/a |
ptnum |
unsigned char |
This field represents the record’s slot number in the database. |
|
System |
system |
oas_sys_name |
The related oas_system record. |