Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA Enterprise SCADA

Jitter Smoothing

  • Last UpdatedJul 05, 2024
  • 1 minute read

The Jitter Smoothing application calculates the average value of analog and rate points processed into AVEVA Enterprise SCADA.

You can configure the number of analog and rate readings–"n"–used in calculating the arithmetic mean.

If the number of available readings is less than "n", the application continues to calculate the average using the available readings until "n" readings are available. The available readings come from analog and rate records' curval and currate fields, respectively.

The application does not modify the actual values received by the host. Instead, it stores the average values for analog and rate points in a separate curavg field.

"n" (Number of Averaged Samples)

Description

Average Value

0

(Default) Disables the calculation of the average value.

Current polled value read.

1

Disables the calculation of the average value.

Current polled value read.

2

Calculate average using the current polled value and the last polled value.

Average of two polled values.

3

Calculate average using the current polled value and the last two polled values.

Average of three polled values.

4

Calculate average using the current polled value and the last three polled values.

Average of four polled values.

.

.

.

16

(Maximum number of samples) Calculate the average using the current polled value and the last 15 polled values.

Average of 16 polled values.

In the following example, the feature is enabled on an analog point by setting "n" to 5:

Polled Value

curval

curavg

10

10

10

20

20

15

30

30

20

40

40

25

50

50

30

60

60

40

70

70

50

80

80

60

90

90

70

100

100

80