Configure analog and rate points
- Last UpdatedApr 24, 2025
- 1 minute read
Follow this procedure to make analog or rate point alarms re-alarm a set number of minutes after you acknowledge them.
Note: In the following procedure, an analog point is used as an example. The procedure is the same for configuring rate points. The Analog Alarm Limits dialog is opened through the Analog Control dialog. For information on Control dialogs, see the AVEVA Enterprise SCADA HMI Controller documentation.
To configure analog and rate points
-
Navigate to the Analog Alarm Limits dialog.

-
In the Realarming Time(Min) field, enter the number of minutes after which an acknowledged alarm should re-alarm.
-
Select Submit.