Configure surge control alarm limits through the Compressor Alarm Limits dialog box.

To configure surge control alarm limits

  1. Under Surge Alarms, select Enabled to enable Surge Control alarming.

  2. In the Flow (X) field, enter the maximum flow rate required to generate a surge alarm (the x-coordinate of a point on the surge control line).

  3. In the Head (Y) field, enter maximum head pressure required to generate a surge alarm (the y-coordinate of a point on the surge control line).

  4. In the Deadband field for Flow (X), enter the x-coordinate (flow) of a point on the surge control deadband line.

  5. In the Deadband field for Head (Y), enter the y-coordinate (head pressure) of a point on the surge control deadband line.

  6. In the Slope field, enter the slope of the surge control line.

    Note: The same slope is also used for the surge warning line.

  7. Under Surge Alarms, select Submit.