Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA Enterprise SCADA

Configure the Realtime_Nom2XML​.json file

  • Last UpdatedApr 24, 2025
  • 1 minute read

Note: For information on overriding default configuration settings, see Modify configuration settings.

  1. If the Realtime_Nom2XML_override.json file exists under %DNADataRoot%\Realtime\config\Settings, open it and proceed to step 3.

    Otherwise, proceed to step 2.

  2. Copy the %DNAInstallRoot%\Realtime\config\Settings\Realtime_Nom2XML.json file to %DNADataRoot%\Realtime\config\Settings, rename it Realtime_Nom2XML_override.json, and open it.

  3. In the file, locate the configuration section for each linked pair of ports that you need to define:

    {

    "RealTime": {

    "Nom2XML": {

    "ServerName": "localhost",

    "PortNumber": 5000,

    "GasContractPrefix": "m",

    "FileFormatType": 0,

    "DebugLevel": 3

    }

    }

    }

  4. Define the following items for the Nom2XML process:

    • ServerName: The hostname or IP Address where the SocketRelayServerService service runs. The default is "localhost".

    • PortNumber: The port number to use. The default is 5000.

    • GasContractPrefix: A prefix added to the point name. The resulting string must match the AVEVA Enterprise SCADA gas contract name. The default prefix is "m".

    • FileFormatType: The file format to use. The default is 0.

      0 is STANDARD_FORMAT:

      <Point Name>,<Point Code>,<Receipt Or Delivery>,<Scheduled Quantity (V)>,<Scheduled Quantity (E)>,<Cycle>,<Gas Day>

      1:

      <Point Code>,<Receipt Or Delivery>,<Scheduled Quantity (V)>,<Scheduled Quantity (E)>,<Cycle>,<Gas Day>

    • DebugLevel: Set the debug level to a value ranging from 3 to 6.

      Where:

      • 3 = DebugLog (default)

      • 4 = Warning

      • 5 = Info

      • 6 = Verbose