Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA Enterprise SCADA

Recreate the Olson time zone database

  • Last UpdatedApr 24, 2025
  • 2 minute read

Before You Begin

Ensure that the computer has the latest cumulative time zones update.

To recreate the Olson time zone database

  1. Copy the rule files from the extracted tzdata<VersionNum> folder into the %DataDir%\Shared\sdk\3rdParty\ZoneInfo\tzdata\ folder.

  2. Open a Windows Command Prompt.

  3. Change the working directory to the %DataDir%\Shared\sdk\3rdParty\ZoneInfo\tzdata\ folder.

  4. Execute the zic.exe command to generate the updated time zone databases.

    For example:

    <full path>\zic.exe -d ..\DB africa antarctica asia australasia

    <full path>\zic.exe -d ..\DB europe northamerica southamerica

    <full path>\zic.exe -d ..\DB etcetera factory backward

    <full path>\zic.exe -d ..\DB windows

    Notes: Specify the full path to the zic compiler instead of just ...\zic.exe.

    It is safe to ignore warning messages that can result in cases where there are differences between the manufacturer's Operating System (OS) interface and the current computer OS, such as the following: ...time zone abbreviation differs from POSIX standard....

    If the system generates a "File exists" error, delete the indicated file from the ..\DB folder and re-run the command.

    The output of the compilation is a set of binary data files, which are saved to the %DataDir%\Shared\sdk\3rdParty\ZoneInfo\DB\ folder.

    Embedded Image (65% Scaling) (LIVE)

  5. Restart all services on the computer, and perform the following, basic tests:

    1. View a trend in easy eXtended Operator Station (ezXOS).

    2. Verify the timestamps of Historical events in ezXOS.

    3. Verify that the times/dates of messages in the oasErrLog.log file are correct.

    4. Verify that the timestamps on polled points within the RealTime database (RTDB) are correct.

  6. Follow the instructions in Deploy the Olson time zone database to deploy the Olson time zone database to all servers.