Rate point configuration
- Last UpdatedApr 24, 2025
- 1 minute read
The rate input and pulse input points are configured through the Input tab in the rate Row Edit dialog box. For full information on the rate table, refer to volume 1 of the AVEVA Enterprise SCADA RealTime Administrator documentation.
Protocol Specific Fields
|
Field |
Description |
|---|---|
|
Point Type |
Select the point type. |
|
Input Coordinates |
Type the PLC-5 data table format: <FileType><FileNumber>:<WordNum> Where: FileType is a one-letter code summarized in the Allen-Bradley File Types table. Refer to Supported file types for point configuration. FileNumber is a decimal number up to three digits in length. WordNum is a decimal number up to three digits in length. |
Rate configuration (example)
|
Rate Input Coordinates (Pulse Input) |
Rate Input Coordinates (Analog Input) |
|---|---|
|
N143:100 |
N143:104 |
The Rate Input Coordinates (Pulse Input) uses the iNteger Type File 143, and reads word 100.
The Rate Input Coordinates (Analog Input) uses the iNteger Type File 143, and reads word 104. Refer to Analog point configuration.