Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA Enterprise SCADA

Test system specifications

  • Last UpdatedApr 24, 2025
  • 1 minute read

The system on which the testing was performed had the following specifications.

Item

Specification

Size of the TimeSeries database

819 GB

Space available in the TimeSeries database

325 GB

Number of rows in TimeSeries Collect

>725 Million

Number of collect rows per tag (for the test points used)

7100 – 7600 (average of 7300)

Clustered?

Yes

Number of cores on the computer

8

Configured for partitioning

No

Everything on one physical disk

No. TimeSeries log and data are on separate disks.

In order to remove issues caused by fragmentation, a full rebuild of the collect, tag, and dataQualityDefine indices was performed prior to running any tests. A reboot of the server was also performed before each batch of tests was run in order to remove any pre-caching of information.

It is important to note that Elk SP4 Historical-Historical Hotfix 7.7.1.4 was in place at the time of testing. In this hotfix, changes were made to the readTimeSeriesCollect Historical procedure to improve the performance of TimeSeries trends. This was accomplished by replacing embedded scalar function calls to getDQName with joins between the collect table and the dataQuality table. This hotfix would only affect reading from the TimeSeries Collect table, and would not affect test results for insert and delete operations.