AVEVA Enterprise SCADA

Analog table

  • Last UpdatedApr 24, 2025
  • 1 minute read

Analog records are used to represent a floating point value. The analog value is stored in the curval field and is often expressed as a measured value such as pressure or voltage. Analog records are located in the analog table and are configured using the analog Row Edit dialog box.

Embedded Image (65% Scaling) (LIVE)

In addition, analog records can be configured for:

  • Conversion of a raw telemetry value into a value in Engineering Units (EGUs).

  • First order smoothing of the raw input value.

  • Setpoint command processing.

  • Complex alarm and event processing on the current analog value.

  • Historical data collection of the current value by exception and at periodic intervals.

  • Current value averaging for the current and previous communications statistics on the primary or alternate paths.

  • Attachment to an Application Calculation Engine (ACE) routine for calculations or control.

From easy eXtended Operator Station (ezXOS), an analog record can be:

  • Manually overridden with a value, or enabled to use the telemetry/calculated value again.

  • Tagged to inhibit setpoint commands.

  • Commanded to send a new setpoint value.

An analog record can also have its alarms inhibited/enabled and its alarm limits changed.