Staling of flowTotalConfig points
- Last UpdatedApr 24, 2025
- 1 minute read
The system sets a flowTotalConfig point to stale if:
-
Any of the contributing telemetered points are:
-
Stale
OR
-
In manual mode
-
-
The source paths for all calculation elements are either blank or disabled.
-
The source path is invalid.
-
All calculation elements in the flowTotalConfig record are disabled.
Note: For the last three stale conditions above, the application also zeros out the calculated values.