Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA Enterprise SCADA

Resolving common errors

  • Last UpdatedApr 24, 2025
  • 1 minute read

Errors detected during execution of the SchemaConverter will be logged to both the screen (standard output), and to the oasErrLog file.

Error/Symptom

Resolution

One or more .json file(s) failed with syntax errors.

Minor adjustments are needed to the affected .json file(s). Start the SchemaConverter process over once adjustments are made to process the correction(s).

.json file failed due to a redeclared type.

This problem generally reflects a RealTime type that has been declared twice. To solve this issue, locate and delete the redundant declaration. You will need to restart the SchemaConverter process.

RealTime will not start-up properly.

This issue often indicates that the database conversion process was not followed correctly, and the RealTime service was restarted before the database was completely reloaded and restored. To resolve this issue:

  1. On the desktop, double-click the Windows PowerShell for DNA shortcut.

    Windows PowerShell for DNA opens.

  2. Execute the following commands to reload the database:

    set-silo RealTime

    loadblankdb.csc

    text_load.csc